| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| FBC B 3107.1, FBC B 1603.1.4, PLEASE PROVIDE THE |
| WINDLOAD DESIGN, PRESSURES AND ALL OTHER WINDLOAD |
| RELATED INFORMATION TO SUPPORT THE STRUCTURAL DESIGN |
| INCLUDING CONNECTIONS. |
| |
| |
| FBC B 107.2.1, PLEASE PROVIDE COMPLETE WELDING |
| DETAILS/ESSENTIAL VARIABLES OF STRUCTURAL CONNECTIONS |
| ON PLANS OR AT TIME OF INSPECTION PLEASE PROVIDE: |
| |
| AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE |
| PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| BE USED. |
| AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE |
| PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |