Plan Review Notes For Permit 20101176 |
Permit Number |
20101176 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-12 13:27:34 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED | | | | 1) OUTDOOR RECEPTACLE REQUIRED ON BACK OF STRUCTURE. | | MUST BE WEATHERPROOF AND GFCI PROTECTED. FBC RE | | E3902.3, E3901.7 | | 2) RECEPTACLE IN LAUNDRY AREA MUST BE GFCI PROTECTED. | | FBC RE E3902.9 | | 3) BEDROOM 2 AND HALLWAY AREA IN FRONT OF BEDROOMS 1 | | AND 2 SEEM TO BE MISSING SOME REQUIRED GENERAL-PURPOSE | | RECEPTACLES. FBC RE E3901.2, FBC RE E3901.10 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|