Plan Review Notes
Plan Review Notes For Permit 20101176
Permit Number 20101176
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-12 13:27:34CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED
  
 1) OUTDOOR RECEPTACLE REQUIRED ON BACK OF STRUCTURE.
 MUST BE WEATHERPROOF AND GFCI PROTECTED. FBC RE
 E3902.3, E3901.7
 2) RECEPTACLE IN LAUNDRY AREA MUST BE GFCI PROTECTED.
 FBC RE E3902.9
 3) BEDROOM 2 AND HALLWAY AREA IN FRONT OF BEDROOMS 1
 AND 2 SEEM TO BE MISSING SOME REQUIRED GENERAL-PURPOSE
 RECEPTACLES. FBC RE E3901.2, FBC RE E3901.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  