Plan Review Notes
Plan Review Notes For Permit 20101168
Permit Number 20101168
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-06 12:53:32RESIDENTIAL (R3) SHUTTERS SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
  
 SHUTTERS INSTALLATION SCHEDULE SUBMITTED:
 1- CONTRACTOR SPECIFIES UNDER THE SUBSTRATE COLUMN THAT
 THERE IS A "SOLID CONCRETE TOP BEAM". THERE ARE NOT
 SPECIFICATIONS FOR THE SUBSTRATE AT THE BOTTOM OF THE
 OPENING. TYPICALLY, THE CONCRETE ANCHOR SCHEDULE IS
 USED FOR TOP ANCHORS AND CONCRETE BLOCK ANCHOR SCHEDULE
 IS USED FOR BOTTOM ANCHORS UNLESS CONTRACTOR PROVES
 THAT THE OPENING SILL IS CONCRETE WITH THE REQUIRED
 CONCRETE STRENGTH.
 CONTRACTOR IS USING THE SAME CONCRETE ANCHOR SCHEDULE
 FOR TOP AND BOTTOM ANCHOR SPACING. REVISE ANCHOR
 SPACING AS REQUIRED OR PROVIDE DETAILS OF THE OPENING
 SILL CONSTRUCTION INCLUDING THE STRENGTH OF THE
 CONCRETE.
  
 RESPONSE:
 COMMENTS WERE NOT ADDRESSED. THE ONLY THING CONTRACTOR
 RESUBMIT WAS A PRINTOUT FROM PAPA. THIS WAS NOT
 REQUESTED AND DOESN'T ADDRESS THE COMMENTS. PLEASE
 REVIEW THE COMMENTS ABOVE AND REVISE THE SHUTTERS
 INSTALLATION SCHEDULE ACCORDINGLY AND RESUBMIT.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  