Plan Review Notes
Plan Review Notes For Permit 20101143
Permit Number 20101143
Review Stop G
Sequence Number 2
Notes
Date Text
2020-12-01 08:55:452ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101143
 12/1/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS #6- 14 FROM THE 1ST REVIEW WERE NOT ADDRESSED.
 PLEASE COMPLY.
  
 6) P3.0: CORRECT THE NOTE SPECIFYING THE ASPHALT PAINT
 ON THE UG GAS LINE- SECTION 404.17 FBC FG.
  
 7) P3.0: CORRECT OR REMOVE NOTE #4 AT THE GENERATOR
 RISER. IT APPEARS NOTE #5 SHOULD BE PROVIDED TO
 INDICATE 2ND STAGE REGULATOR. SHOW THE REQUIRED PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR-
 SECTIONS 410.1 & 410.2(7) FBC FG, AND SECTION 107.2.1
 WPB. PLEASE SHOW OR NOTE THE REQUIRED PIPE UNIONS AT
 THE REGULATOR LOCATED ON THE EXTERIOR WALL.
  
 8) P3.0: INDICATE A FLEXIBLE GAS SUPPLY LINE WILL BE
 INSTALLED AT THE GENERATOR AND PROVIDE THE LENGTH AND
 SIZE- SECTION 411.1 FBC FG.
  
 9) P1.0 & P3.0: SINGLE DEDICATED AND ACCESSIBLE SHUT
 OFF VALVES FOR THE EQUIPMENT IN THE MAIN LAB ROOM AND
 IN THE EQUIPMENT/COMPRESSOR ROOM SHALL BE PROVIDED. THE
 VALVES SHALL SERVE AS MAIN SHUTOFFS FOR ALL EQUIPMENT
 IN EACH ROOM AND SHALL BE LOCATED ADJACENT TO THE
 EGRESS DOOR FROM THE ROOM OR SPACE, AND SHALL BE
 IDENTIFIED BY APPROVED SIGNAGE STATING "GAS SHUTOFF"-
 SECTION 409.6 FBC FG.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND INTERIOR GAS-FIRED EQUIPMENT. THE SPECS
 SHALL BE HIGHLIGHTED OR MARKED UP TO SHOW THE MBTU/H
 LOADS, INPUT PRESSURES, AND LISTING STANDARDS- SECTIONS
 301.3, 301.5, & 305.1 FBC FG.
  
 11) CLARIFY IF THE INTERIOR EQUIPMENT WILL BE DIRECTLY
 CONNECTED VIA THE RIGID PIPING OR IF APPLIANCE
 CONNECTORS OR QUICK DISCONNECT DEVICES WILL BE
 INSTALLED. SUBMIT SPECS FOR ALL MANUFACTURED CONNECTORS
 HIGHLIGHTED OR MARKED UP TO SHOW LISTINGS- SECTION
 411.1 FBC FG.
  
 12) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 INTERIOR GAS-FIRED EQUIPMENT AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SECTION 304.1 & 305.1 FBC FG.
  
 13) PLEASE REFER TO SECTION 501.8 ITEMS #10 & 11 FBC
 FG: VENTING SYSTEMS APPEAR NOT TO BE REQUIRED FOR THE
 GAS BURNERS BECAUSE THE TOTAL GAS LOAD IN EACH ROOM
 DOES NOT EXCEED 20 MBTU/H, HOWEVER PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR THE EQUIPMENT TO CONFIRM COMPLIANCE- SECTION 305.1
 FBC FG.
  
 14) REFER TO SECTION 307.2 FBC FG AND PROVIDE
 CONDENSATE DISPOSAL PLANS FOR EQUIPMENT PRODUCING
 LIQUID COMBUSTION BY PRODUCTS.
  
 NEW COMMENT:
  
 15) INDICATE HOW THE GENERATOR IN THE PARKING LOT WILL
 BE PROTECTED FROM DAMAGE BY VEHICULAR IMPACT- SECTION
 303.4 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  