2020-12-01 08:55:45 | 2ND REVIEW FBC-2017 FUEL GAS |
| PERMIT- 20101143 |
| 12/1/2020 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS #6- 14 FROM THE 1ST REVIEW WERE NOT ADDRESSED. |
| PLEASE COMPLY. |
| |
| 6) P3.0: CORRECT THE NOTE SPECIFYING THE ASPHALT PAINT |
| ON THE UG GAS LINE- SECTION 404.17 FBC FG. |
| |
| 7) P3.0: CORRECT OR REMOVE NOTE #4 AT THE GENERATOR |
| RISER. IT APPEARS NOTE #5 SHOULD BE PROVIDED TO |
| INDICATE 2ND STAGE REGULATOR. SHOW THE REQUIRED PIPE |
| UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- |
| SECTIONS 410.1 & 410.2(7) FBC FG, AND SECTION 107.2.1 |
| WPB. PLEASE SHOW OR NOTE THE REQUIRED PIPE UNIONS AT |
| THE REGULATOR LOCATED ON THE EXTERIOR WALL. |
| |
| 8) P3.0: INDICATE A FLEXIBLE GAS SUPPLY LINE WILL BE |
| INSTALLED AT THE GENERATOR AND PROVIDE THE LENGTH AND |
| SIZE- SECTION 411.1 FBC FG. |
| |
| 9) P1.0 & P3.0: SINGLE DEDICATED AND ACCESSIBLE SHUT |
| OFF VALVES FOR THE EQUIPMENT IN THE MAIN LAB ROOM AND |
| IN THE EQUIPMENT/COMPRESSOR ROOM SHALL BE PROVIDED. THE |
| VALVES SHALL SERVE AS MAIN SHUTOFFS FOR ALL EQUIPMENT |
| IN EACH ROOM AND SHALL BE LOCATED ADJACENT TO THE |
| EGRESS DOOR FROM THE ROOM OR SPACE, AND SHALL BE |
| IDENTIFIED BY APPROVED SIGNAGE STATING "GAS SHUTOFF"- |
| SECTION 409.6 FBC FG. |
| |
| 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| GENERATOR AND INTERIOR GAS-FIRED EQUIPMENT. THE SPECS |
| SHALL BE HIGHLIGHTED OR MARKED UP TO SHOW THE MBTU/H |
| LOADS, INPUT PRESSURES, AND LISTING STANDARDS- SECTIONS |
| 301.3, 301.5, & 305.1 FBC FG. |
| |
| 11) CLARIFY IF THE INTERIOR EQUIPMENT WILL BE DIRECTLY |
| CONNECTED VIA THE RIGID PIPING OR IF APPLIANCE |
| CONNECTORS OR QUICK DISCONNECT DEVICES WILL BE |
| INSTALLED. SUBMIT SPECS FOR ALL MANUFACTURED CONNECTORS |
| HIGHLIGHTED OR MARKED UP TO SHOW LISTINGS- SECTION |
| 411.1 FBC FG. |
| |
| 12) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| INTERIOR GAS-FIRED EQUIPMENT AND INDICATE HOW THE AIR |
| WILL BE PROVIDED- SECTION 304.1 & 305.1 FBC FG. |
| |
| 13) PLEASE REFER TO SECTION 501.8 ITEMS #10 & 11 FBC |
| FG: VENTING SYSTEMS APPEAR NOT TO BE REQUIRED FOR THE |
| GAS BURNERS BECAUSE THE TOTAL GAS LOAD IN EACH ROOM |
| DOES NOT EXCEED 20 MBTU/H, HOWEVER PLEASE SUBMIT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS |
| FOR THE EQUIPMENT TO CONFIRM COMPLIANCE- SECTION 305.1 |
| FBC FG. |
| |
| 14) REFER TO SECTION 307.2 FBC FG AND PROVIDE |
| CONDENSATE DISPOSAL PLANS FOR EQUIPMENT PRODUCING |
| LIQUID COMBUSTION BY PRODUCTS. |
| |
| NEW COMMENT: |
| |
| 15) INDICATE HOW THE GENERATOR IN THE PARKING LOT WILL |
| BE PROTECTED FROM DAMAGE BY VEHICULAR IMPACT- SECTION |
| 303.4 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |