Date |
Text |
2020-12-07 09:32:47 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT- 20101143 |
| 11/19/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P4.0 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| THE COMPRESSORS, COMPRESSED AIR PIPING, AND PIPE |
| CONNECTORS TO EQUIPMENT- SECTION 1003.1 AND 1003.2 FBC |
| M. THE SPECS SHALL SHOW THE MAXIMUM PRESSURE RATINGS OF |
| THE COMPRESSORS, PIPING, AND CONNECTORS. |
| |
| 2) P4.0: INDICATE ON THE PLAN THE TYPE OF COMPRESSED |
| AIR PIPING AND PIPE SLEEVES TO BE INSTALLED- SECTION |
| 1003.2 FBC M. PROVIDE PIPE SUPPORT AND HANGING DETAILS- |
| TYPES, SIZES, AND SPACINGS OF HANGERS. |
| |
| 3) P4.0: SUBMIT SPECS FOR THE AIR INTAKES AT THE |
| EXTERIOR WALL AND PROVIDE A DETAIL SHOWING HOW THE AIR |
| WILL BE DUCTED TO THE CEILING AIR INTAKE. CLARIFY HOW |
| THE AMOUNT OF REQUIRED AIR FOR THE COMPRESSOR ROOM WAS |
| DETERMINED OR CALCULATED- SECTION 107.2.1 WPB. |
| |
| 4) P4.0: SHOW HOW CONDENSATION FROM THE COMPRESSORS |
| WILL BE DRAINED AND DISPOSED OF- SECTION 307.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |