2020-11-16 16:00:16 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| |
| 1) SHEET NUMBER E-3.0 KEYNOTE NUMBER 2 STATES THAT |
| GENERATOR IS NOT A SEPARATELY DERIVED SYSTEM. RISER |
| DIAGRAMS SHOWS A #6 GROUND AT THE GENERATOR. FOR |
| GENERATORS INSTALLED AS NOT SEPARATELY DERIVED SYSTEM |
| NORMALLY THE EQUIPMENT GROUNDING CONDUCTOR THAT IS PART |
| OF THE FIVE WIRE FEEDER FROM THE GENERATOR TO THE |
| TRANSFER EQUIPMENT WILL GROUND AND BOND ALL OF THE |
| NON-CURRENT CARRYING METAL PARTS OF THE GENERATOR |
| THROUGH THE TRANSFER EQUIPMENT TO THE GROUNDING |
| ELECTRODE SYSTEM BACK AT THE SERVICE. NEC 250.35. ONLY |
| ONE FAULT RETURN PATH SHOULD EXIST. |
| 2) PROVIDE NOTE REQUIRING WARNING LABEL TO COMPLY WITH |
| NEC 702.7 |
| 3) SEE SIGNATURE COMMENTS. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |