2020-11-16 16:00:16CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SHEET NUMBER E-3.0 KEYNOTE NUMBER 2 STATES THAT
 GENERATOR IS NOT A SEPARATELY DERIVED SYSTEM. RISER
 DIAGRAMS SHOWS A #6 GROUND AT THE GENERATOR. FOR
 GENERATORS INSTALLED AS NOT SEPARATELY DERIVED SYSTEM
 NORMALLY THE EQUIPMENT GROUNDING CONDUCTOR THAT IS PART
 OF THE FIVE WIRE FEEDER FROM THE GENERATOR TO THE
 TRANSFER EQUIPMENT WILL GROUND AND BOND ALL OF THE
 NON-CURRENT CARRYING METAL PARTS OF THE GENERATOR
 THROUGH THE TRANSFER EQUIPMENT TO THE GROUNDING
 ELECTRODE SYSTEM BACK AT THE SERVICE. NEC 250.35. ONLY
 ONE FAULT RETURN PATH SHOULD EXIST.
 2) PROVIDE NOTE REQUIRING WARNING LABEL TO COMPLY WITH
 NEC 702.7
 3) SEE SIGNATURE COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  