Plan Review Notes
Plan Review Notes For Permit 20101143
Permit Number 20101143
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-17 13:27:45GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW CONCRETE GENERATOR PAD THICKNESS AND ANY
 REQUIRED REINFORCEMENT. FBC 1901.2
 2) PLEASE PROVIDE SIGNED AND SEALED GENERATOR TIEDOWN
 REQUIREMENTS SHOWING THE WIND DESIGN DATA USED FROM AN
 ARCHITECT OR ENGINEER PER FBC 1603.1 TO COMPLY WITH THE
 REQUIRED WIND LOADS PER FBC 1609
 3) PLEASE SHOW THE CONCRETE PAD SETBACKS FROM THE
 PROPERTY LINES AND THE WATER RUN OFF TO BE MAINTAINED
 ON THIS PROPERTY.
  