Plan Review Notes
Plan Review Notes For Permit 20101141
Permit Number 20101141
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-10-26 14:33:09FIRE PROVISO COMMENTS
  
  
  
 1) PULL STATIONS ARE INDICATED AT EACH EXIT (3). PER
 NFPA 101 CH 12 AND CH 9 PULL STATIONS ARE NOT REQUIRED.
  
 IN AN EFFORT TO REDUCE FALSE FIRE ALARMS THESE PULL
 STATIONS CAN BE REMOVED.
  
 12.3.4.2 INITIATION.
 12.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 BOTH OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS
 OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (A) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT
 PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING.
 (B) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT
 PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE
 BUILDING.
 (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION
 OF THE
 FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN
 WHERE
 MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH
 12.3.4.2.1(1)
  
  
 2) DUCT DETECTORS ARE INDICATED.
  
 1) THERE ARE INDICATIONS THAT A DUCT DETECTOR WILL
 CAUSE A FULL FIRE ALARM ACTIVATION. NFPA PROVIDES CODE
 REFERENCES FOR SUPERVISORY SIGNAL ACTIVATION.
  
 PER NFPA 90A, 2015 ED.
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4
 ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN
 APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE
 FOLLOWING SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
 PER NFPA 72, 2013 ED
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET
 THE REQUIREMENTS OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A
 CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION
 SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM
 SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES,
 OR STANDARDS.
  
 PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION.
  
  
 PETER LEDUC
 FIRE MARSHAL