Plan Review Notes
Plan Review Notes For Permit 20101101
Permit Number 20101101
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-19 22:33:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEPARATE ELECTRICAL PERMIT REQUIRED BY LICENSED
 ELECTRICIAN FOR 120V BRANCH CIRCUIT WORK. OUT OF SCOPE
 FOR ES LICENSE. PLEASE REFERENCE ELECTRICAL PERMIT
 NUMBER OF SAID PERMIT WHEN RESUBMITTING. FBC 105.1 .FS.
 489.505 (#19) AND F.A.C. 61G6-7.001 SPECIALTY
 ELECTRICAL CONTRACTORS (#2 SIGN SPECIALTY CONTRACTOR)
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW SHOWING POWER
 SUPPLY, DISCONNECTS, ETC. FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved