2020-12-09 17:00:34 | RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| ORIGINAL COMMENT: |
| COMMENTS TO DRAWING CVR SUBMITTED: |
| 1)OK |
| 2)OK |
| |
| 3) CONSTRUCTION DRAWINGS ARE NOT CLEAR AND ARE |
| INCOMPLETE: |
| A)PROVIDE DETAIL SHOWING HOW ARE THE 2X4 STUDS |
| INSTALLED UNDER THE EXISTING PRECAST CONCRETE DOUBLE |
| TEE FLOORING AND SPECIFY FASTENER TYPE, SIZE AND |
| SPACING. |
| SEC. R703.1.2.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. DRAWING SUBMITTED STILL NO CLEAR AND |
| DOESN'T PROVIDE SPECIFICATIONS FOR FASTENING OF P.T. |
| 2X4"S TO THE PRECAST DOUBLE TEE FLOORING. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B)FASTENING OF THE PLYWOOD IS NOT CLEAR. WHERE ARE THE |
| (2)3" TAPCONS PLACED. SPECIFY SPACING, ETC. COORDINATE |
| WITH ITEM #3. ABOVE. |
| SEC. R703.1.2.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. FASTENING OF THE PLYWOOD IS NOT CLEAR. |
| SPECIFICATIONS SHOWN ON THE CONSTRUCTION PLAN DON'T |
| MATCH SPECIFICATIONS SHOWN ON THE CONSTRUCTION |
| AXONOMETRIC. CLEARLY SPECIFY FASTENER TYPE, SIZE AND |
| SPACING. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS |
| AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. THERE ARE NO SPECIFICATIONS FOR 2 |
| LAYERS OF WATER RESISTIVE BARRIERS. THERE IS A NOTE ON |
| THE CONSTRUCTION AXONOMETRIC CALLING FOR "DOUBLE WIRE |
| LATH". CLARIFY WHAT IS THIS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| NEW COMMENTS: |
| D)CONSTRUCTION AXONOMETRIC SHOWS "EXISTING RAILING TO |
| REMAIN" ON THE UPPER ROOF. ACCORDING TO PHOTOS SHOWN ON |
| SHEET CVR, THERE IS NOT RAILING ON THE ROOF. |
| REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| E)CONSTRUCTION AXONOMETRIC CALLS FOR "INSTALL A 3" PVC |
| VENT. ACCORDING TO CONTRACTOR THERE IS NOT WORK ON THE |
| SECOND FLOOR ROOF, EXCEPT FOR A MINOR REPAIR/PATCH. |
| REVISE/CLARIFY AS REQUIRED. IF INSTALLING VENT , THEN |
| CLEARLY SPECIFY SIZE AND LOCATION OF VENTS. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |