2020-12-03 13:15:07 | RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| ORIGINAL COMMENT: |
| 1-UNABLE TO PERFORM BUILDING REVIEW. THERE IS NOT |
| INFORMATION TO REVIEW. PROVIDE COMPLETE SET OF |
| DRAWINGS/SPECIFICATIONS SHOWING ALL THE SCOPE OF WORK |
| TO BE PERFORMED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| COMMENTS TO DRAWING CVR SUBMITTED: |
| 1)DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT OF |
| RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS REQUIRED |
| BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN SUBMITTING |
| DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS. |
| |
| 2) DRAWING HAS A NOTE ACROSS ENTIRE SHEET STATING THAT |
| THIS IS NOT FOR CONSTRUCTION. NEED TO PROVIDE DRAWING |
| WITHOUT THIS NOTE. DRAWING IS SUBMITTED FOR |
| CONSTRUCTION. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3) CONSTRUCTION DRAWINGS ARE NOT CLEAR AND ARE |
| INCOMPLETE: |
| A)PROVIDE DETAIL SHOWING HOW ARE THE 2X4 STUDS |
| INSTALLED UNDER THE EXISTING PRECAST CONCRETE DOUBLE |
| TEE FLOORING AND SPECIFY FASTENER TYPE, SIZE AND |
| SPACING. |
| SEC. R703.1.2.1 FBC-RESIDENTIAL. |
| |
| B)FASTENING OF THE PLYWOOD IS NOT CLEAR. WHERE ARE THE |
| (2)3" TAPCONS PLACED. SPECIFY SPACING, ETC. COORDINATE |
| WITH ITEM #3. ABOVE. |
| SEC. R703.1.2.1 FBC-RESIDENTIAL. |
| |
| C)DRAWINGS DON'T PROVIDE ANY INFORMATION ABOUT THE |
| FINISH MATERIALS ON THIS SOFFIT. IS IT STUCCO?. SPECIFY |
| THICKNESS ( TABLE R702.1(1). FBC-RESIDENTIAL). |
| |
| D) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS |
| AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL. |
| |
| |