2020-11-16 15:19:20RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1-UNABLE TO PERFORM BUILDING REVIEW. THERE IS NOT
 INFORMATION TO REVIEW. PROVIDE COMPLETE SET OF
 DRAWINGS/SPECIFICATIONS SHOWING ALL THE SCOPE OF WORK
 TO BE PERFORMED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 INFORMATION SUBMITTED:
 A) IT LOOKS LIKE THE FIRST FLOOR SOFFIT AND THE SECOND
 FLOOR SOFFIT CONSTRUCTION ARE DIFFERENT. INFORMATION
 SUBMITTED IS NOT CLEAR. WHERE ARE THE COLUMNS SPECIFIED
 ON THE INFORMATION SUBMITTED. PROVIDE A COMPLETE
 DRAWING WITH COMPLETE SPECIFICATIONS FOR EACH TYPE OF
 SOFFIT SHOWING THAT THE SOFFIT IS DESIGNED TO RESIST
 THE WIND LOADS AS REQUIRED BY SEC. R703.1.2.1
 FBC-RESIDENTIAL. (NOTE: ACCORDING TO SEC. R301.2.1.4
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "D". HAVE THIS IN CONSIDERATION FOR THE WIND RESISTANCE
 REQUIRED FOR THIS SOFFIT).
  
 B) PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,