2020-12-09 10:52:41PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE NEW LOAD CALCULATIONS.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
  
 2. PROVIDE NEW PANEL SCHEDULE.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 3. PROVIDE KITCHEN OUTLET SPACING.
 E3901.4 COUNTERTOP RECEPTACLES.
 IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND
 SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR
 COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTIONS E3901.4.1 THROUGH E3901.4.5 (SEE FIGURE
 E3901.4). [210.52(C)]
  
 NOTICE:
 TWO 20 AMP SMALL APPLIANCE BRANCH CIRCUTS REQUIRED.
 NEC 210.52 (B) (3) ? KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 4. WALL COUNTER TOP SPACING.
 E3901.4.1 WALL COUNTERTOP SPACE.
 A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM),
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. [210.52(C)(1)]
  
 5. PROVIDE SMOKE ALARMS
 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING.
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 R314.3 LOCATION.
 R314.4 INTERCONNECTION.
  
 6. R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
 FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 R314.5 COMBINATION ALARMS.
 COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE
 PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS.
  
 7. DISHWASHER OUTLET SHALL BE GFCI PROTECTED.
 E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
  
 8. PROVIDE LOCATION OF ALL OUTLETS ON PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NOTICE:
 GROUND-FAULT AND ARC-FAULT CIRCUIT-INTERRUPTER
 PROTECTION REQUIRED.
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  