2020-12-09 10:52:41 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2014 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE NEW LOAD CALCULATIONS. |
| PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| NEC 220; FBC RE E3602.2 |
| |
| 2. PROVIDE NEW PANEL SCHEDULE. |
| PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| |
| 3. PROVIDE KITCHEN OUTLET SPACING. |
| E3901.4 COUNTERTOP RECEPTACLES. |
| IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| SECTIONS E3901.4.1 THROUGH E3901.4.5 (SEE FIGURE |
| E3901.4). [210.52(C)] |
| |
| NOTICE: |
| TWO 20 AMP SMALL APPLIANCE BRANCH CIRCUTS REQUIRED. |
| NEC 210.52 (B) (3) ? KITCHEN COUNTER TOP RECEPTACLES |
| SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE |
| BRANCH CIRCUITS. |
| |
| 4. WALL COUNTER TOP SPACING. |
| E3901.4.1 WALL COUNTERTOP SPACE. |
| A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER. |
| RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM), |
| MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| SPACE. [210.52(C)(1)] |
| |
| 5. PROVIDE SMOKE ALARMS |
| 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING. |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| R314.3 LOCATION. |
| R314.4 INTERCONNECTION. |
| |
| 6. R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| FEET OF EACH SLEEPING ROOM. |
| R314.5 COMBINATION ALARMS. |
| COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE |
| PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS. |
| |
| 7. DISHWASHER OUTLET SHALL BE GFCI PROTECTED. |
| E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. |
| GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE |
| PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN |
| DWELLING UNIT LOCATIONS. [210.8(D)] |
| |
| 8. PROVIDE LOCATION OF ALL OUTLETS ON PLAN. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| NOTICE: |
| GROUND-FAULT AND ARC-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION REQUIRED. |
| E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |