Plan Review Notes
Plan Review Notes For Permit 20101028
Permit Number 20101028
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-27 12:09:47JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. PROVIDE FLOOR PLANS/BUILDING
 FOOTPRINT SHOWING LOCATION OF PROPOSED WINDOWS TO BE
 REPLACED ALONG WITH DIMENSIONS OF EACH OPENING; WINDOW
 TYPE AND ROOM DESIGNATION.
 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED MULLION BARS TO BE
 USED (IF APPLICABLE). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
  