2021-05-11 08:18:33 | 3RD REVIEW FBC-2017 PLUMBING |
| PERMIT-20100983 |
| 5/10/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P0.1, P2.1 & P5.1: HAND SINK SK-2 SHALL NOT |
| DRAIN INTO THE GREASE INTERCEPTOR- SECTION 1003.3.1 FBC |
| P. HANDSINKS ARE NOT SIGNIFICANT GREASE CONTRIBUTORS. |
| |
| 2) P0.1, P2.1, & P5.1: THE PLANS SHOW A DIRECT WASTE |
| CONNECTION FOR SK-1 HOWEVER AN INDIRECT WASTE |
| CONNECTION IS REQUIRED PER SECTIONS 802.1 & 802.1.1 FBC |
| P. THE PLANS DO NOT MAKE CLEAR THE USE OF THE SINK BUT |
| IT IS ASSUMED TO BE RELATED TO EITHER FOOD PREP OR |
| DISHWASHING. |
| |
| 3) P0.1, P2.1, & P6.1: THE NOTES IN THE SCHEDULE FOR |
| SK-4 INDICATE COMPLIANCE WITH SECTION 422.6 FBC P. |
| PLEASE REFER TO TABLE 604.5 AND CLARIFY IF THE SELECTED |
| SINK IS A CLINAL SINK WITH A FLUSHOMETER VALVE BECAUSE |
| A 1-INCH WATER LINE IS REQUIRED AND THE PLANS SHOW A |
| 1/2- INCH LINE. |
| |
| 4) P0.2: PLEASE PROVIDE A SAMPLING PORT DETAIL FOR THE |
| GREASE INTERCEPTOR- SECTION 1003.3.4 FBC P. |
| |
| 5) P0.2, P2.1: PLEASE NOTE THAT A LOAD RATED TRAFFIC |
| LID SHALL BE PROVIDED FOR THE INTERCEPTOR IF LOCATED IN |
| A MOTOR VEHICLE DRIVE OR PARKING AREA- SECTION 1003.3.4 |
| FBC P. |
| |
| 6) P0.2 & P2.1: PROVIDE SIZING CALCULATIONS FOR THE |
| STRIEM SOLIDS INTERCEPTOR TO VERIFY ADEQUATE GALLON |
| SIZE SIZE SELECTION. THE SPECS SHOW 2 IN. INLETS AND |
| OUTLETS, HOWEVER THE SANITARY RISER INDICATES 4 INCH |
| PIPE CONNECTIONS. REFER TO SECTION 1003.6 FBC P- PLEASE |
| VERIFY THE INTERCEPTOR IS PROVIDED WITH A WIRE BASKET |
| OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT |
| PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2 |
| INCH OR LARGER IN SIZE, STRING, RAGS, BUTTONS OR OTHER |
| MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE SYSTEM. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |