Plan Review Notes
Plan Review Notes For Permit 20100983
Permit Number 20100983
Review Stop M
Sequence Number 3
Notes
Date Text
2021-05-10 09:09:373RD REVIEW FBC-2020 MECHANICAL
 PERMIT-20100983
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET LS-1-1 SHOWS 1-HOUR RATED CORRIDOR WALLS.
 SHEET M2-1: PLEASE SHOW THE REQUIRED PROTECTION WHERE
 ALL CORRIDOR WALLS ARE PENETRATED BY THE MECHANICAL
 DUCTS. I.E. AHU-6 DUCTWORK INTO THE MUSIC ROOM. FBC M
 607
  
 2) SHEET M2-1: PLEASE SHOW PROTECTION AT EACH LOCATION
 THAT THE 12 X14 DUCT FROM OAU-3 PENETRATES THE RATED
 CORRIDOR WALLS. FBC 607
  
 3) SHEET M2-1: PLEASE SHOW PROTECTION AT EACH LOCATION
 THAT THE BATH EXHAUST DUCTS PENETRATE THE FIRE
 PARTITION SEPARATING THE SLEEPING UNITS. FBC 607
  
 4) PLEASE SHOW HOW AHU-3, AHU-6 AND AHU-1 MEET AIR
 MOVEMENT IN EGRESS ELEMENTS FBC M 601.2
  
 5) PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS
 INDICATING THAT THE KITCHEN HOOD WILL BE A SEPARATE
 SUBMITTAL AND REVIEW. IT WILL ALSO NEED TO MEET FBC M
 506, 507 FOR THE HOOD AND GREASE DUCT, SECTION 508 FOR
 MAKE UP AIR, SECTION 509 FOR FIRE SUPPRESSION SYSTEMS.
 THE HOOD EXHAUST MUST MEET FBC M 501.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  