Plan Review Notes For Permit 20100983
Permit Number 20100983
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-26 17:34:462ND REVIEW FBC-2017 PLUMBING
 PERMIT-20100983
 2/26/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. REMAINING COMMENTS FROM
 THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 3) SHEET LS.1.1 & LS.1.1, PLUMBING FIXTURE
 REQUIREMENTS: THE SQUARE FOOT AREAS AND OCCUPANT LOADS
 ON LS.1.1 DO NOT MATCH THE AREA AND OCCUPANT LOAD CALCS
 IN THE PLUMBING FIXTURE SCHEDULE ON LS.1.2. PLEASE
 CORRECT. THE NARRATIVE RESPONSE STATES THIS HAS BEEN
 CLEARED UP IN PHONE CALL, HOWEVER THE REVIEWER HAS
 NUMEROUS PHONE CALLS ABOUT PLANS, AND UNFORTUNATELY
 DOES NOT RECALL THE DETAILS OF THE PHONE CALL. PLEASE
 SUBMIT A NARRATIVE IN WRITING CLARIFYING WHAT THE
 DESIGN INTENTION IS REGARDING THE NUMBER OF REQUIRED
 FIXTURES FOR THE OCCUPANCY, AND THE REQUIRED SEPARATION
 OF FACILITIES FOR MALE AND FEMALE USE IN THE BUSINESS
 AND ASSEMBLY AREAS.
  
 B) FAILED. LIST THE REQUIRED AND PROVIDED NUMBERS OF
 MALE AND FEMALE WATER CLOSETS AND LAVATORIES FOR A3, B,
 R4, & S OCCUPANCIES. PLEASE NOTE THAT SEPARATE MALE AND
 FEMALE FIXTURES ARE REQUIRED FOR A3, B AND S
 OCCUPANCIES- SECTION 403.2. UNISEX ARE PERMITTED FOR
 THE R4 OCCUPANCY. SEPARATE MALE AND FEMALE FIXTURES
 REQUIRED.
  
 6) FAILED. P0.1, P2.1 & P5.1: A) SK-1 &SK-2 ARE
 MISLABELED L2 IN THE ISOMETRIC. B) SK-3 IS MISLABELED
 SK-2 IN THE ISOMETRIC. C) SK-3 IS A 3-COMPARTMENT SINK
 PER THE FIXTURE SCHEDULE BUT IS SHOWN AS A
 2-COMPARTMENT SINK ON THE PLAN, AND A SINGLE SINK IN
 THE ISO. INDIRECT WASTE REQUIRED FOR THE 3-BAY SINK-
 SECTIONS 802.1 & 802.1.1 FBC P.
  
 8) FAILED. P0.1: PROVIDE AN ITEMIZED FOOD EQUIPMENT
 PLAN AND CORRELATING EQUIPMENT SCHEDULE- SECTION
 107.2.1 WPB. CLARIFY WHAT EQUIPMENT MAY BE INSTALLED IN
 THE KITCHEN SUCH AS A FOOD WASTE DISPOSER, ICE MAKER,
 BEVERAGE DISPENSER, COFFEE MAKER ETC. THE SCHEDULE ON
 SHEET A10.04 SHOWS AN ELECTRIC RANGE, THE GAS PLAN ON
 SHEET P3.1 SHOWS A GAS RANGE. REFER TO GAS REIVEW
 COMMENTS.
  
 9) FAILED P0.1, P2.1 & P5.1: PROVIDE A GREASE
 INTERCEPTOR AND GREASE INTERCEPTOR CALCULATIONS FOR THE
 DRAINAGE FROM PLUMBING FIXTURES IN THE KITCHEN- REFER
 TO SECTIONS 1003.1 & 1003.3.1 FBC P. REVISE THE
 DRAWINGS AND SPECIFICATIONS TO SHOW THE TYPE OF
 INTERCEPTOR TO BE INSTALLED, MAKE AND MODEL OF THE
 UNIT, THE LOCATION AND THE PLUMBING PIPING
 REQUIREMENTS. SECTION 1003.3.3 DOES NOT REQUIRE GREASE
 INTERCEPTORS FOR INDIVIDUAL DWELLING UNITS AND PRIVATE
 QUARTERS. THIS OCCUPANCY IS A GROUP LIVING FACILITY.
 EXCEPTION DOES NOT APPLY- PROVIDE THE GREASE
 INTERCEPTOR AS REQUIRED.
  
 10) FAILED. P0.1, P2.1 & P5.1: THE DRAINAGE FROM THE
 DISHWASHER AND THE 2 OR 3-COMPARTMENT SINKS SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE RECEPTOR- SECTIONS
 802.1 & 802.7 FBC P. REVISE THE DRAWINGS ACCORDINGLY,
 PROVIDE AN INSTALLATION DETAIL PER SECTION 802.2, AND
 ADD THE RECEPTORS TO THE FIXTURE SCHEDULES- SECTION
 802.3. THE FIXTURE SCHEDULE ON SHEET P0.1 CALLS OUT A
 COMMERCIAL DISHWASHER.
  
 11) FAILED. P0.1, P2.1 & P5.1: PROVIDE INTERCEPTORS FOR
 THE CLOTHES WASHERS PER SECTION 1003.6. REVISE THE
 DRAWINGS AND SPECIFICATIONS TO SHOW MAKES AND MODELS OF
 THE UNITS, LOCATIONS, AND THE PLUMBING PIPING
 REQUIREMENTS. THE EXCEPTIONS UNDER 1003.6 ARE NOT
 APPLICABLE.
  
 13) FAILED. P0.1, P5.1, & P6.1: SK-4 IS MISLABELED AS
 SK-1 IN THE ISOMETRIC DRAWINGS- SECTION 107.2.1 WPB.
 BASED ON THE USE OF THE MEDICATION ROOM, A CLINICAL
 SINK SHALL BE REQUIRED IN ACCORDANCE WITH SECTIONS
 422.1 & 422.6. REVISE THE DRAWINGS AND THE SCHEDULE
 ACCORDINGLY. SK-4 DRAIN NOT SHOWN CORERECTLY IN THE
 ISOMETRIC ON P5.1. SINK HAS AN INTEGRAL TRAP- SEE
 SECTION 713.2 FBC P.
  
 14) FAILED. P3.1 & P6.1: IF APPLICABLE TO THE KITCHEN
 LAYOUT PLEASE SHOW THE WATER SUPPLY LINES TO EQUIPMENT
 SUCH AS ICE MAKERS OR BEVERAGE DISPENSERS AND THE
 REQUIRED WATER HAMMER ARRESTORS AND BACKFLOW
 PREVENTERS- SECTIONS 604.9 AND 608.3 FBC P. SHOW HOW
 THE DISHWASHER WILL BE PROTECTED AGAINST BACKFLOW-
 SECTION 409.2. THE FIXTURE SCHEDULE ON SHEET P0.1 CALLS
 OUT A COMMERCIAL DISHWASHER, HOWEVER ALL DISHWASHING
 MACHINES WHETHER RESIDENTIAL OR COMMERCIAL REQUIRE SOME
 TYPE OGF BACKFLOW PREVENTION- SEE P2717.1 FBC RES.
  
 20) FAILED CORRECT THE ENERGY COMPLIANCE IECC- 2015
 FORM INDICATING THE WATER HEATER IS LESS THAN 75000
 BTUH- THE EQUIPMENT SCHEDULE INDICATES 200,000 BTUH.
 PLEASE CORRECT THE DATA AND PROVIDE THE MISSING PIPING
 SYSTEM COMPLIANCE DATA- SECTION C101.5 FBC EC. THE
 COMPLIANCE DATA IN THE CALCS INDICATES 155,000 BTUH OR
 LESS. EFFICENCY REQUIREMENT IS THE SAME PER THE TABLE,
 HOWEVER THE PLANS AND CALCS MUST MATCH. PLEASE SHOW THE
 GAS PIPING CONNECTION. SEE GAS REVIEW COMMENTS.
  
 21) FAILED. PROVIDE A ROOF DRAINAGE PLAN INCLUDING ROOF
 FLOW RATE CALCULATIONS, AND SIZING OF THE HORIZONTAL
 ROOF GUTTER AND VERTICAL LEADER SIZES PER SECTIONS
 1106.3, 1106.6 AND TABLES 1106.3 & 1106.6 FBC P.
 NARRATIVE REFERECNES SHEET A.2.0.1 WHICH IS NOT A
 COMPLETE ROOF DRAINAGE PLAN. REFER TO SECTIONS AND
 TABLES 1106.3 &1106.6 FBC P. PLEASE PROVIDE GUTTER AND
 DOWNSPOUT ATTACHMENT DETAILS- SECTIONS 1101.2 & 1102.7.
  
 22) SHEETS A10.01- A10.02 FAIR HOUSING ACT DESIGN
 MANUAL GUIDELINES:
  
 A) FAILED. PROVIDE GRAB BAR REINFORCEMENT DETAILS FOR
 ALL BATH FIXTURES- PAGE 7.33 (REQUIREMENT 6). PLEASE
 NOTE SPECIFICATION TYPE B SHOWERS REQUIRE
 REINFORCEMENTS FOR FUTURE SEATS- PAGE 7.5. NOT PROVIDED
 ON A10.01 & A-10.02.
  
 B) FAILED. INDICATE WHICH DESIGN HAS BEEN SELECTED FOR
 THE RESIDENT ROOMS- SPECIFICATION TYPE A OR TYPE B-
 PAGE 7.34. NOT PROVIDED.
  
 F) FAILED. PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE TOILETS- PAGE 7.43- 7.46. DIMENSIONS
 NOT PROVIDED.
  
 G) FAILED. A FRONT APPROACH TO THE LAVATORY SINKS IS
 SHOWN PROVIDE A DETAIL FOR INSTALLATION OF THE
 REMOVABLE LAVATORY CABINET OR BASE- PAGE 7.49. FAIR
 HOUSING SINK DETAIL NOT PROVIDED.
 23) SHEET A10.0.3:
  
 E) FAILED. THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM
 FROM THE CENTERLINE OF THE SEAT TOWARD THE SHOWER
 OPENING. PLEASE CORRECT THE INCORRECT DIMENSION SHOWN
 IN DETAIL 9/A10.03- SECTION 608.5.1. PLEASE INDICATE
 THE CENTER OF THE SHOWER SEAT ACCORDING TO THE CODE
 SECTION.
  
 26) A10.06:
  
 C) FAILED. SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF
 THE LAVATORY SINKS- SECTION 306.3.NOT PROVIDED.
  
 27) A10.0.7:
  
 B) FAILED. SHOW THE REQUIRED 30 X 60 IN. CLEARANCE
 DIAGRAMS AND DIMENSIONS AT THE SHOWERS- SECTION
 608.2.2.1. 30 IN. WIDTH DIMENSION NOT PROVIDED.
  
 C) FAILED. SHOW THE SHOWER GRAB BARS WILL BE INSTALLED
 A MAXIMUM OF 6 IN. FROM THE ADJACENT WALLS- SECTION AND
 FIGURE 608.3.2. NOT PROVIDED.
  
 E) FAILED. PROVIDE A ROLL-IN SHOWER PAN AND THRESHOLD
 DETAIL- SECTION 608.7 FBC P AND SECTION 417.5.2 FBC P.
 NOT PROVIDED.
  
 G) FAILED. SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF
 THE LAVATORY SINKS- SECTION 306.3. MINIMUM 11 IN. WIDE
 KNEE CLEARANCE NOT SHOWN- SEE FIGURE 306.3.
  
 28) FAILED. ACCESSIBLE DRINKING FOUNTAINS: PROVIDE
 DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B)
 KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, SPOUT
 LOCATIONS- SECTIONS 306, 307, & 602.2. C) COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS. SHEET LS.1.2 -
 MINIMUM 11 IN. WIDE KNEE CLEARANCE NOT SHOWN- SEE
 FIGURE 306.3. PLEASE WRITE "SPOUT HEIGHT" ON THE
 DETAIL.
  
 29) NEW COMMENT- SHEET P6.1: THE NEW SK-4 REQUIRES ?
 IN. SUPPLY LINES. PLEASE CORRECT THE ISO- SECTION 422.6
 AND TABLE 604.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  