2021-02-26 17:34:46 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT-20100983 |
| 2/26/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. REMAINING COMMENTS FROM |
| THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| |
| 3) SHEET LS.1.1 & LS.1.1, PLUMBING FIXTURE |
| REQUIREMENTS: THE SQUARE FOOT AREAS AND OCCUPANT LOADS |
| ON LS.1.1 DO NOT MATCH THE AREA AND OCCUPANT LOAD CALCS |
| IN THE PLUMBING FIXTURE SCHEDULE ON LS.1.2. PLEASE |
| CORRECT. THE NARRATIVE RESPONSE STATES THIS HAS BEEN |
| CLEARED UP IN PHONE CALL, HOWEVER THE REVIEWER HAS |
| NUMEROUS PHONE CALLS ABOUT PLANS, AND UNFORTUNATELY |
| DOES NOT RECALL THE DETAILS OF THE PHONE CALL. PLEASE |
| SUBMIT A NARRATIVE IN WRITING CLARIFYING WHAT THE |
| DESIGN INTENTION IS REGARDING THE NUMBER OF REQUIRED |
| FIXTURES FOR THE OCCUPANCY, AND THE REQUIRED SEPARATION |
| OF FACILITIES FOR MALE AND FEMALE USE IN THE BUSINESS |
| AND ASSEMBLY AREAS. |
| |
| B) FAILED. LIST THE REQUIRED AND PROVIDED NUMBERS OF |
| MALE AND FEMALE WATER CLOSETS AND LAVATORIES FOR A3, B, |
| R4, & S OCCUPANCIES. PLEASE NOTE THAT SEPARATE MALE AND |
| FEMALE FIXTURES ARE REQUIRED FOR A3, B AND S |
| OCCUPANCIES- SECTION 403.2. UNISEX ARE PERMITTED FOR |
| THE R4 OCCUPANCY. SEPARATE MALE AND FEMALE FIXTURES |
| REQUIRED. |
| |
| 6) FAILED. P0.1, P2.1 & P5.1: A) SK-1 &SK-2 ARE |
| MISLABELED L2 IN THE ISOMETRIC. B) SK-3 IS MISLABELED |
| SK-2 IN THE ISOMETRIC. C) SK-3 IS A 3-COMPARTMENT SINK |
| PER THE FIXTURE SCHEDULE BUT IS SHOWN AS A |
| 2-COMPARTMENT SINK ON THE PLAN, AND A SINGLE SINK IN |
| THE ISO. INDIRECT WASTE REQUIRED FOR THE 3-BAY SINK- |
| SECTIONS 802.1 & 802.1.1 FBC P. |
| |
| 8) FAILED. P0.1: PROVIDE AN ITEMIZED FOOD EQUIPMENT |
| PLAN AND CORRELATING EQUIPMENT SCHEDULE- SECTION |
| 107.2.1 WPB. CLARIFY WHAT EQUIPMENT MAY BE INSTALLED IN |
| THE KITCHEN SUCH AS A FOOD WASTE DISPOSER, ICE MAKER, |
| BEVERAGE DISPENSER, COFFEE MAKER ETC. THE SCHEDULE ON |
| SHEET A10.04 SHOWS AN ELECTRIC RANGE, THE GAS PLAN ON |
| SHEET P3.1 SHOWS A GAS RANGE. REFER TO GAS REIVEW |
| COMMENTS. |
| |
| 9) FAILED P0.1, P2.1 & P5.1: PROVIDE A GREASE |
| INTERCEPTOR AND GREASE INTERCEPTOR CALCULATIONS FOR THE |
| DRAINAGE FROM PLUMBING FIXTURES IN THE KITCHEN- REFER |
| TO SECTIONS 1003.1 & 1003.3.1 FBC P. REVISE THE |
| DRAWINGS AND SPECIFICATIONS TO SHOW THE TYPE OF |
| INTERCEPTOR TO BE INSTALLED, MAKE AND MODEL OF THE |
| UNIT, THE LOCATION AND THE PLUMBING PIPING |
| REQUIREMENTS. SECTION 1003.3.3 DOES NOT REQUIRE GREASE |
| INTERCEPTORS FOR INDIVIDUAL DWELLING UNITS AND PRIVATE |
| QUARTERS. THIS OCCUPANCY IS A GROUP LIVING FACILITY. |
| EXCEPTION DOES NOT APPLY- PROVIDE THE GREASE |
| INTERCEPTOR AS REQUIRED. |
| |
| 10) FAILED. P0.1, P2.1 & P5.1: THE DRAINAGE FROM THE |
| DISHWASHER AND THE 2 OR 3-COMPARTMENT SINKS SHALL |
| DISCHARGE THROUGH AN INDIRECT WASTE RECEPTOR- SECTIONS |
| 802.1 & 802.7 FBC P. REVISE THE DRAWINGS ACCORDINGLY, |
| PROVIDE AN INSTALLATION DETAIL PER SECTION 802.2, AND |
| ADD THE RECEPTORS TO THE FIXTURE SCHEDULES- SECTION |
| 802.3. THE FIXTURE SCHEDULE ON SHEET P0.1 CALLS OUT A |
| COMMERCIAL DISHWASHER. |
| |
| 11) FAILED. P0.1, P2.1 & P5.1: PROVIDE INTERCEPTORS FOR |
| THE CLOTHES WASHERS PER SECTION 1003.6. REVISE THE |
| DRAWINGS AND SPECIFICATIONS TO SHOW MAKES AND MODELS OF |
| THE UNITS, LOCATIONS, AND THE PLUMBING PIPING |
| REQUIREMENTS. THE EXCEPTIONS UNDER 1003.6 ARE NOT |
| APPLICABLE. |
| |
| 13) FAILED. P0.1, P5.1, & P6.1: SK-4 IS MISLABELED AS |
| SK-1 IN THE ISOMETRIC DRAWINGS- SECTION 107.2.1 WPB. |
| BASED ON THE USE OF THE MEDICATION ROOM, A CLINICAL |
| SINK SHALL BE REQUIRED IN ACCORDANCE WITH SECTIONS |
| 422.1 & 422.6. REVISE THE DRAWINGS AND THE SCHEDULE |
| ACCORDINGLY. SK-4 DRAIN NOT SHOWN CORERECTLY IN THE |
| ISOMETRIC ON P5.1. SINK HAS AN INTEGRAL TRAP- SEE |
| SECTION 713.2 FBC P. |
| |
| 14) FAILED. P3.1 & P6.1: IF APPLICABLE TO THE KITCHEN |
| LAYOUT PLEASE SHOW THE WATER SUPPLY LINES TO EQUIPMENT |
| SUCH AS ICE MAKERS OR BEVERAGE DISPENSERS AND THE |
| REQUIRED WATER HAMMER ARRESTORS AND BACKFLOW |
| PREVENTERS- SECTIONS 604.9 AND 608.3 FBC P. SHOW HOW |
| THE DISHWASHER WILL BE PROTECTED AGAINST BACKFLOW- |
| SECTION 409.2. THE FIXTURE SCHEDULE ON SHEET P0.1 CALLS |
| OUT A COMMERCIAL DISHWASHER, HOWEVER ALL DISHWASHING |
| MACHINES WHETHER RESIDENTIAL OR COMMERCIAL REQUIRE SOME |
| TYPE OGF BACKFLOW PREVENTION- SEE P2717.1 FBC RES. |
| |
| 20) FAILED CORRECT THE ENERGY COMPLIANCE IECC- 2015 |
| FORM INDICATING THE WATER HEATER IS LESS THAN 75000 |
| BTUH- THE EQUIPMENT SCHEDULE INDICATES 200,000 BTUH. |
| PLEASE CORRECT THE DATA AND PROVIDE THE MISSING PIPING |
| SYSTEM COMPLIANCE DATA- SECTION C101.5 FBC EC. THE |
| COMPLIANCE DATA IN THE CALCS INDICATES 155,000 BTUH OR |
| LESS. EFFICENCY REQUIREMENT IS THE SAME PER THE TABLE, |
| HOWEVER THE PLANS AND CALCS MUST MATCH. PLEASE SHOW THE |
| GAS PIPING CONNECTION. SEE GAS REVIEW COMMENTS. |
| |
| 21) FAILED. PROVIDE A ROOF DRAINAGE PLAN INCLUDING ROOF |
| FLOW RATE CALCULATIONS, AND SIZING OF THE HORIZONTAL |
| ROOF GUTTER AND VERTICAL LEADER SIZES PER SECTIONS |
| 1106.3, 1106.6 AND TABLES 1106.3 & 1106.6 FBC P. |
| NARRATIVE REFERECNES SHEET A.2.0.1 WHICH IS NOT A |
| COMPLETE ROOF DRAINAGE PLAN. REFER TO SECTIONS AND |
| TABLES 1106.3 &1106.6 FBC P. PLEASE PROVIDE GUTTER AND |
| DOWNSPOUT ATTACHMENT DETAILS- SECTIONS 1101.2 & 1102.7. |
| |
| 22) SHEETS A10.01- A10.02 FAIR HOUSING ACT DESIGN |
| MANUAL GUIDELINES: |
| |
| A) FAILED. PROVIDE GRAB BAR REINFORCEMENT DETAILS FOR |
| ALL BATH FIXTURES- PAGE 7.33 (REQUIREMENT 6). PLEASE |
| NOTE SPECIFICATION TYPE B SHOWERS REQUIRE |
| REINFORCEMENTS FOR FUTURE SEATS- PAGE 7.5. NOT PROVIDED |
| ON A10.01 & A-10.02. |
| |
| B) FAILED. INDICATE WHICH DESIGN HAS BEEN SELECTED FOR |
| THE RESIDENT ROOMS- SPECIFICATION TYPE A OR TYPE B- |
| PAGE 7.34. NOT PROVIDED. |
| |
| F) FAILED. PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND |
| DIMENSIONS FOR THE TOILETS- PAGE 7.43- 7.46. DIMENSIONS |
| NOT PROVIDED. |
| |
| G) FAILED. A FRONT APPROACH TO THE LAVATORY SINKS IS |
| SHOWN PROVIDE A DETAIL FOR INSTALLATION OF THE |
| REMOVABLE LAVATORY CABINET OR BASE- PAGE 7.49. FAIR |
| HOUSING SINK DETAIL NOT PROVIDED. |
| 23) SHEET A10.0.3: |
| |
| E) FAILED. THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT |
| SHALL BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM |
| FROM THE CENTERLINE OF THE SEAT TOWARD THE SHOWER |
| OPENING. PLEASE CORRECT THE INCORRECT DIMENSION SHOWN |
| IN DETAIL 9/A10.03- SECTION 608.5.1. PLEASE INDICATE |
| THE CENTER OF THE SHOWER SEAT ACCORDING TO THE CODE |
| SECTION. |
| |
| 26) A10.06: |
| |
| C) FAILED. SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF |
| THE LAVATORY SINKS- SECTION 306.3.NOT PROVIDED. |
| |
| 27) A10.0.7: |
| |
| B) FAILED. SHOW THE REQUIRED 30 X 60 IN. CLEARANCE |
| DIAGRAMS AND DIMENSIONS AT THE SHOWERS- SECTION |
| 608.2.2.1. 30 IN. WIDTH DIMENSION NOT PROVIDED. |
| |
| C) FAILED. SHOW THE SHOWER GRAB BARS WILL BE INSTALLED |
| A MAXIMUM OF 6 IN. FROM THE ADJACENT WALLS- SECTION AND |
| FIGURE 608.3.2. NOT PROVIDED. |
| |
| E) FAILED. PROVIDE A ROLL-IN SHOWER PAN AND THRESHOLD |
| DETAIL- SECTION 608.7 FBC P AND SECTION 417.5.2 FBC P. |
| NOT PROVIDED. |
| |
| G) FAILED. SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF |
| THE LAVATORY SINKS- SECTION 306.3. MINIMUM 11 IN. WIDE |
| KNEE CLEARANCE NOT SHOWN- SEE FIGURE 306.3. |
| |
| 28) FAILED. ACCESSIBLE DRINKING FOUNTAINS: PROVIDE |
| DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR |
| FLOOR SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR |
| ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B) |
| KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, SPOUT |
| LOCATIONS- SECTIONS 306, 307, & 602.2. C) COMPLIANCE |
| WITH SECTION 307.2 PROTRUSION LIMITS. SHEET LS.1.2 - |
| MINIMUM 11 IN. WIDE KNEE CLEARANCE NOT SHOWN- SEE |
| FIGURE 306.3. PLEASE WRITE "SPOUT HEIGHT" ON THE |
| DETAIL. |
| |
| 29) NEW COMMENT- SHEET P6.1: THE NEW SK-4 REQUIRES ? |
| IN. SUPPLY LINES. PLEASE CORRECT THE ISO- SECTION 422.6 |
| AND TABLE 604.3 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |