Plan Review Notes
Plan Review Notes For Permit 20100983
Permit Number 20100983
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2020-11-13 14:36:151) SP-1 IS A PART OF THE DESIGN OF THIS PROJECT AND FS
 471 REQUIRES THE DESIGNER TO SIGN AND SEAL THE
 DRAWINGS. BECAUSE THIS IS A DIGITAL SUBMITTAL WE NEED
 THIS TO BE A DIGITAL SIGNATURE AND SEAL. FBC 481
 2) THE CIVIL SHEETS ARE DIGITALLY SIGNED AND SEALED BY
 THE ENGINEER HOWEVER 61G15-23.004 F.A.C.REQUIRES THE
 ENGINEER TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
 3) SHEET SP-0-3 DOES NOT HAVE A DITITAL SIGNATURE OR
 SEAL FROM THE ARCHITECT. IT DOES REQUIRE A DIGITAL
 SIGNATURE AND SEAL. FS 481.
 4) SHEET S-4- THE ENGINEER DID DIGITALLY SIGN AND SEAL
 THIS SHEET BUT 61G15-23.004 F.A.C. REQUIRES THE
 ENGINEER TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
 5) THE GEOTECH REPORT IS DIGITALLY SIGNED AND SEALED BY
 THE ENGINEER BUT 61G15-23.004 F.A.C. REQUIRES THE
 ENGINEER TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  