2020-11-06 14:03:261ST REVIEW FBC-2017 PLUMBING
 PERMIT-20100983
 11/6/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE SEPARATE PERMITS ARE REQUIRED FOR THE
 WATER SERVICE BACKFLOW PREVENTER, IRRIGATION SYSTEM,
 GAS PIPING SYSTEM, EMERGENCY GENERATOR, AND GREASE
 INTERCEPTOR- SECTION 107.2.1 WPB. COMPLETE PLANS AND
 SPECIFICATIONS ARE REQUIRED FOR REVIEW.
 2) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 3) SHEET LS.1.1 PLUMBING FIXTURE REQUIREMENTS SCHEDULE
 CORRECTIONS PER SECTION 403 & TABLE 403.3 FBC P.
  
 A) ROUND UP THE FRACTIONAL NUMBERS- SECTION 403.1.1 FBC
 P.
  
 B) LIST THE REQUIRED AND PROVIDED NUMBERS OF MALE AND
 FEMALE WATER CLOSETS AND LAVATORIES FOR A3, B, R4, & S
 OCCUPANCIES. PLEASE NOTE THAT SEPARATE MALE AND FEMALE
 FIXTURES ARE REQUIRED FOR A3, B AND S OCCUPANCIES-
 SECTION 403.2. UNISEX ARE PERMITTED FOR THE R4
 OCCUPANCY.
  
 C) LIST THE REQUIRED AND PROVIDED NUMBER OF SERVICE
 SINKS AND DRINKING FOUNTAINS- TABLE 403.3 FBC P.
  
 4) SHEET P2.1: PROVIDE A CLEANOUT AT THE JUNCTION OF
 THE BUILDING DRAIN AND SEWER- SECTION 708.1.3 FBC P.
  
 5) SHEETS P2.1 & P5.1: THE PLAN INDICATES ISLAND SINKS
 AND DISHWASHER BUT THE ISOMETRIC DRAWING SHOWS A VENT
 STACK INSTEAD OF AN ISLAND VENT OR AAV- SECTION 916 FBC
 P.
  
 6) P0.1, P2.1 & P5.1: A) SK-1 &SK-2 ARE MISLABELED L2
 IN THE ISOMETRIC. B) SK-3 IS MISLABELED SK-2 IN THE
 ISOMETRIC. C) SK-3 IS A 3-COMPARTMENT SINK PER THE
 FIXTURE SCHEDULE BUT IS SHOWN AS A 2-COMPARTMENT SINK
 ON THE PLAN, AND A SINGLE SINK IN THE ISO.
  
 7) P0.1 PLUMBING FIXTURE SCHEDULE: PLEASE INCLUDE THE
 SHOWER VALVES TO BE INSTALLED IN THE ACCESSIBLE AND
 NON-ACCESSIBLE SHOWERS- SECTION 608.6 FBC ACC AND 424.3
 FBC P.
  
 8) P0.1: PROVIDE AN ITEMIZED FOOD EQUIPMENT PLAN AND
 CORRELATING EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB.
 CLARIFY WHAT EQUIPMENT MAY BE INSTALLED IN THE KITCHEN
 SUCH AS A FOOD WASTE DISPOSER, ICE MAKER, BEVERAGE
 DISPENSER, COFFEE MAKER ETC.
  
 9) P0.1, P2.1 & P5.1: PROVIDE A GREASE INTERCEPTOR AND
 GREASE INTERCEPTOR CALCULATIONS FOR THE DRAINAGE FROM
 PLUMBING FIXTURES IN THE KITCHEN- REFER TO SECTIONS
 1003.1 & 1003.3.1 FBC P. REVISE THE DRAWINGS AND
 SPECIFICATIONS TO SHOW THE TYPE OF INTERCEPTOR TO BE
 INSTALLED, MAKE AND MODEL OF THE UNIT, THE LOCATION AND
 THE PLUMBING PIPING REQUIREMENTS.
  
 10) P0.1, P2.1 & P5.1: THE DRAINAGE FROM THE DISHWASHER
 AND THE 2 OR 3-COMPARTMENT SINKS SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE RECEPTOR- SECTIONS 802.1 &
 802.7 FBC P. REVISE THE DRAWINGS ACCORDINGLY, PROVIDE
 AN INSTALLATION DETAIL PER SECTION 802.2, AND ADD THE
 RECEPTORS TO THE FIXTURE SCHEDULES- SECTION 802.3.
  
 11) P0.1, P2.1 & P5.1: PROVIDE INTERCEPTORS FOR THE
 CLOTHES WASHERS PER SECTION 1003.6. REVISE THE DRAWINGS
 AND SPECIFICATIONS TO SHOW MAKES AND MODELS OF THE
 UNITS, LOCATIONS, AND THE PLUMBING PIPING REQUIREMENTS.
  
 12) P3.1 & P6.1: A) SK-3 IS MISLABELED SK-2 IN THE
 ISOMETRIC. B) SK-3 IS A 3-COMPARTMENT SINK PER THE
 FIXTURE SCHEDULE BUT IS SHOWN AS A 2-COMPARTMENT SINK
 ON THE PLAN, AND A SINGLE SINK IN THE ISO. C) P3.1
 SHOWS SK-1 & SK-2 COUNTER SINKS, P6.1 SHOWS DOUBLE SK-1
 SINKS.
  
 13) P0.1, P5.1, & P6.1: SK-4 IS MISLABELED AS SK-1 IN
 THE ISOMETRIC DRAWINGS- SECTION 107.2.1 WPB. BASED ON
 THE USE OF THE MEDICATION ROOM, A CLINICAL SINK SHALL
 BE REQUIRED IN ACCORDANCE WITH SECTIONS 422.1 & 422.6.
 REVISE THE DRAWINGS AND THE SCHEDULE ACCORDINGLY.
  
 14) P3.1 & P6.1: IF APPLICABLE TO THE KITCHEN LAYOUT
 PLEASE SHOW THE WATER SUPPLY LINES TO EQUIPMENT SUCH AS
 ICE MAKERS OR BEVERAGE DISPENSERS AND THE REQUIRED
 WATER HAMMER ARRESTORS AND BACKFLOW PREVENTERS-
 SECTIONS 604.9 AND 608.3 FBC P. SHOW HOW THE DISHWASHER
 WILL BE PROTECTED AGAINST BACKFLOW- SECTION 409.2.
  
 15) P3.1 & P6.1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SECTIONS 416.5 & 607.1.2.
  
 16) P0.1: PROVIDE A PLUMBING DEVICE SCHEDULE INDICATING
 MAKES AND MODELS AND LISTINGS OF THE RECIRCULATION
 PUMPS, BALANCING VALVES, FULL OPEN SHUTOFF VALVES,
 WATER HAMMER ARRESTORS, TRAP PRIMERS, BACKFLOW
 PREVENTERS, AND MIXING VALVES ETC.- SECTIONS 604.9,
 606, 607.1.2, 607.2.1, 608.3, 613.1 FBC P AND 107.2.1
 WPB.
  
 17) P3.1: INDICATE HOW ACCESS WILL BE PROVIDED TO THE
 BALANCING VALVES- SECTION 606.3.
  
 18) P0.1 & P3.1: SHOW WATER HEATER RELIEF VALVE PIPE,
 DRAIN PAN AND DRAIN PIPE DETAILS- SECTION 504 FBC P.
  
 19) P0.1 & P3.1: INDICATE THE RECIRCULATION PUMP
 CONTROLS SHALL START THE PUMPS BASED ON THE
 IDENTIFICATION OF A DEMAND FOR HOT WATER WITHIN THE
 OCCUPANCY, AND SHALL AUTOMATICALLY TURN OFF THE PUMP
 WHEN THE WATER IN THE CIRCULATION LOOP IS AT THE
 DESIRED TEMPERATURE AND WHEN THERE IS NO DEMAND FOR HOT
 WATER- SECTION 607.2.1 FBC P AND SECTION R403.5.1.1 FBC
 EC.
  
 20) CORRECT THE ENERGY COMPLIANCE IECC- 2015 FORM
 INDICATING THE WATER HEATER IS LESS THAN 75000 BTUH-
 THE EQUIPMENT SCHEDULE INDICATES 200,000 BTUH. PLEASE
 CORRECT THE DATA, AND PROVIDE THE MISSING PIPING SYSTEM
 COMPLIANCE DATA- SECTION C101.5 FBC EC.
  
 21) PROVIDE A ROOF DRAINAGE PLAN INCLUDING ROOF FLOW
 RATE CALCULATIONS, AND SIZING OF THE HORIZONTAL ROOF
 GUTTER AND VERTICAL LEADER SIZES PER SECTIONS 1106.3,
 1106.6 AND TABLES 1106.3 & 1106.6 FBC P.
  
 22) SHEETS A10.01- A10.02 FAIR HOUSING ACT DESIGN
 MANUAL GUIDELINES:
  
 A) PROVIDE GRAB BAR REINFORCEMENT DETAILS FOR ALL BATH
 FIXTURES- PAGE 7.33 (REQUIREMENT 6). PLEASE NOTE
 SPECIFICATION TYPE B SHOWERS REQUIRE REINFORCEMENTS FOR
 FUTURE SEATS- PAGE 7.58.
  
 B) INDICATE WHICH DESIGN HAS BEEN SELECTED FOR THE
 RESIDENT ROOMS- SPECIFICATION TYPE A OR TYPE B- PAGE
 7.34.
  
 C) THE SHOWERS SHALL NOT BE INSTALLED ADJACENT TO THE
 TOILETS- PAGE 7.44. PLEASE RE-DESIGN THE LAYOUT TO BE
 IN COMPLIANCE.
  
 D) THE SHOWER CONTROLS SHALL BE INSTALLED ON THE
 OPPOSITE WALL OF WHERE THEY ARE SHOWN ON THE PLAN- PAGE
 7.56.
  
 E) SHOW THE REQUIRED MINIMUM 36 X 36 IN. SHOWER
 DIMENSIONS- PAGE 7.58.
  
 F) PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE TOILETS- PAGE 7.43- 7.46.
  
 G) A FRONT APPROACH TO THE LAVATORY SINKS IS SHOWN
 PROVIDE A DETAIL FOR INSTALLATION OF THE REMOVABLE
 LAVATORY CABINET OR BASE- PAGE 7.49.
  
 23) SHEET A10.0.3:
  
 A) PROVIDE THE CLEAR FLOOR SPACE DIMENSION FOR THE
 WATER CLOSET MEASURED PERPENDICULAR FROM THE REAR WALL-
 SECTION 604.3.1 FBC ACC.
  
 B) SHOW THE MOUNTING HEIGHTS OF FIXTURE GRAB BARS
 MEASURED FROM THE FINISH FLOORS TO THE TOPS OF THE
 GRIPPING SURFACES- SECTION 609.4
  
 C) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SECTION 604.6.
  
 D) THE LENGTHS OF THE SHOWER GRAB BARS AS SHOWN IN
 DETAILS 2, 9, & 10 ARE NOT IN COMPLIANCE WITH FIGURE
 608.3.1 FBC ACC.
  
 E) THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL
 BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM
 THE CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.
 PLEASE CORRECT THE INCORRECT DIMENSION SHOWN IN DETAIL
 9- SECTION 608.5.1.
  
 F) CORRECT THE 1/8 IN. SHOWER SLOPE SHOWN IN THE DETAIL
 TO INDICATE 1/4 IN. PER FT.- SECTION 417.5.2 FBC P.
 SHOW THE LINER TURNED UP NOT LESS THAN 2? ABOVE THE
 FINISHED THRESHOLD ON ALL SIDES. PLEASE NOTE THAT
 RECESSED SHOWERS SHALL BE DEPRESSED A MINIMUM OF 2 IN.
 BELOW THE FINISHED FLOOR.
  
 24) A10.04: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS AT THE KITCHEN SINKS- SECTION 606.2 FBC ACC.
  
 25) A10.05: SHOW THE REQUIRED CLEAR FLOOR SPACE
 PARALLEL APPROACHES FOR THE WASHERS AND DRYERS- SECTION
 611.2. A) SHOW THE MEASUREMENTS TO THE BOTTOM AND TOP
 OF THE WASHER AND DRYER DOOR OPENINGS MEASURED FROM THE
 FINISHED FLOOR- SECTION 611.4 FBC ACC. C) INDICATE THE
 WASHER AND DRYER CONTROLS ARE IN COMPLIANCE WITH
 SECTIONS 309.3, 309.4 & 611.3 FBC ACC.
  
 26) A10.06:
  
 A) SHOW THE MOUNTING HEIGHTS OF FIXTURE GRAB BARS
 MEASURED FROM THE FINISH FLOORS TO THE TOPS OF THE
 GRIPPING SURFACES- SECTION 609.4 FBC ACC.
  
 B) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SECTION 604.6.
  
 C) SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF THE
 LAVATORY SINKS- SECTION 306.3.
  
 D) THE TOILET PAPER DISPENSER SHALL BE INSTALLED WITH
 THE CENTERLINE OF THE DISPENSER LOCATED BETWEEN 7 AND 9
 IN. FROM THE FRONT OF THE WATER CLOSET- SECTION 604.7.
  
 E) SEE COMMENT #13 REGARDING THE MEDICATION SINK.
 PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE SINK IN DETAIL 1- SECTIONS 212.3 AND
 606.2.
 27) A10.0.7:
  
 A) SHOW THE REQUIRED 30 X 60 IN. DIMENSIONS OF THE
 SHOWERS- SECTION AND FIGURE 608.2.2 FBC ACC.
  
 B) SHOW THE REQUIRED 30 X 60 IN. CLEARANCE DIAGRAMS AND
 DIMENSIONS AT THE SHOWERS- SECTION 608.2.2.1.
  
 C) SHOW THE SHOWER GRAB BARS WILL BE INSTALLED A
 MAXIMUM OF 6 IN. FROM THE ADJACENT WALLS- SECTION AND
 FIGURE 608.3.2.
  
 D) SHOW THE HEIGHT OF THE SHOWER CONTROL MEASURED FROM
 THE FINISHED FLOOR OF THE SHOWER- SECTION 608.5.2.
  
 E) PROVIDE A ROLL-IN SHOWER PAN AND THRESHOLD DETAIL-
 SECTION 608.7 FBC P AND SECTION 417.5.2 FBC P.
  
 F) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SECTION 604.6 FBC ACC.
  
 G) SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF THE
 LAVATORY SINKS- SECTION 306.3.
  
 H) THE TOILET PAPER DISPENSER SHALL BE INSTALLED WITH
 THE CENTERLINE OF THE DISPENSER LOCATED BETWEEN 7 AND 9
 IN. FROM THE FRONT OF THE WATER CLOSET- SECTION 604.7.
  
 28) ACCESSIBLE DRINKING FOUNTAINS: PROVIDE DRAWINGS AND
 DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B) KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS-
 SECTIONS 306, 307, & 602.2. C) COMPLIANCE WITH SECTION
 307.2 PROTRUSION LIMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER