Plan Review Notes
Plan Review Notes For Permit 20100983
Permit Number 20100983
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-13 13:20:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100983
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LS-1.2 LISTS THE MULTIPURPOSE ROOM OCCUPANCY AS 18.
 SHEET M0.1 OUTSIDE AIR CALCULATIONS HAS THE OCCUPANCY
 FOR THE MULTIPURPOSE ROOM AT 8. PLEASE MAKE THE OUTSIDE
 AIR CALCULATIONS OCCUPANCY COUNT MATCH THE BUILDING
 OCCUPANCY COUNT FOR USE OF SPACE. FBC M TABLE 4.3.3.1.1
  
 2) PLEASE USE THE BUILDING OCCUPANT COUNT FOR USE OF
 SPACE AS THE ?ACTUAL OCCUPANT NO. OF PEOPLE IN THE
 OUTSIDE AIR CALCULATIONS. FBC TABLE 403.3.1.1
  
 3) PLEASE SHOW ON THE MECHANICAL DRAWINGS THAT THE
 AHU?S FOR THE LIVING QUARTERS ARE ACCESSIBLE. FBC M
 306.3 APPLIANCES IN ATTICS
  
 4) SHEET M2.1; THE WALL BETWEEN THE GAME ROOM AND THE
 RECEPTION AREAS APPEARS TO BE A RATED WALL. PLEASE SHOW
 THE PROTECTION AT THE PENETRATIONS OF THESE RATED WALLS
 FOR THE SUPPLY AND RETURN DUCTS FOR THE GAME ROOM. FBC
 M 607
  
 5) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE COOKING
 EQUIPMENT IN THE KITCHEN. PLEASE PROVIDE A DETAIL OF
 THE SPECIFIC USE OF THIS KITCHEN AND TYPES OF FOOD
 BEING PREPARED. FBC 107.2
  
 6) PLEASE PROVIDE SPECIFICATIONS FOR THE KITCHEN HOOD.
 FBC M 507
  
 7) EXHAUST FANS IN THE BATHROOMS IN THE WORKOUT ROOM DO
 NOT HAVE A TAG ASSOCIATED WITH GENERAL FAN SCHEDULE ON
 SHEET M6.2 PLEASE CORRECTLY IDENTIFY THESE EXHAUST
 FANS. FBC 107.2
  
 8) PLEASE PROVIDE A DETAIL DRAWING OF THE BATH EXHAUST
 FANS AND THE FIRE DAMPER LOCATION AND ACCESS. FBC M
 607.4
  
 9) PLEASE SHOW ACCESS FOR EACH FIRE SMOKE DAMPER. FBC
 M607.4
  
 10) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE DRYERS
 IN THE LAUNDRY ROOM. FBC M 504
  
 11) SHEET M7.2 THE DETAIL DRAWING OF THE DRYER ROOF
 TERMINATION HAS A SCREEN AT THE EXHAUST TERMINATION.
 PLEASE REMOVE THE SCREEN AS IT IS NOT ALLOWED. FBC M
 504.4
  
 12) SHEET M7.2 THE CEILING FIRE DAMPER DETAIL INDICATES
 THERE IS A CEILING BELOW THE RATED CEILING, PLEASE
 PROVIDE A SHEET NUMBER THAT SHOWS THE DETAIL OF THE TWO
 CEILINGS. FBC 107.2
  
 13)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  