Date |
Text |
2021-02-26 17:40:01 | 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT- 20100983 |
| 2/26/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P6.1: PROVIDE MANUFACTURER?S SPECIFICATIONS |
| FOR THE GENERATOR, RANGE, AND DRYERS- SECTION 107.2.1 |
| WPB. CONCERNING THE GENERATOR, A SEPARATE PERMIT IS |
| REQUIRED FOR THE INSTALLATION, HOWEVER A CUT SHEET |
| SHOWING THE BTUH LOAD AND INPUT PRESSURE WOULD BE |
| HELPFUL FOR REGULATOR SELECTION- SECTION 410.2 FBC FG. |
| PLEASE NOTE THAT THE CURRENT RANGE PRODUCT SUBMITTAL IS |
| FOR AN ELECTRIC APPLIANCE, AND THE GAS DRYER SUBMITTAL |
| INDICATES 22,000 BTUH DRYERS- THE RISER SHOWS 75,000 |
| BTUH DRYERS. |
| |
| 2) P6.1: SHOW THE TOTAL LOAD OF THE SYSTEM- 3,377,000 |
| BTUH- SECTION 402.2 & 402.3 FBC FG. |
| |
| 3) P6.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| RANGE AND DRYERS AND INDICATE HOW THE AIR WILL BE |
| PROVIDED- SECTION 304.1 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |