2020-12-07 17:08:14 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E.1.1 | | | | GAZEBO HAS MORE THAN ONE BRANCH CIRCUIT GOING TO IT. IT | | SHALL MEET THE REQUIREMENTS OF 225.30 | | | | A BUILDING OR O THER STRUCTURE THAT IS SERVED BY A | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN 225.30(A) | | THROUGH (E). FOR THE PURPOSE OF THIS SECTION, A | | MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE | | CIRCUIT. | | | | PAGE E3.1 | | | | DRINKING FOUNTAN SHALL BE GFCI PROTECTED AND GFCI | | DEVICE SHALL BE ACCESSIBLE 422.52 | | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | | PAGE E5.1 | | | | TRANSFER SWITCH DOES NOT SHOW A SIZE OR BREAKER SIZE | | INSIDE. 215.5 | | | | GENERATOR SHOW OCP NO SIZE SHOWN. 215.5 |
|