2020-11-02 16:42:471ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100957
 11/2/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER
 DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES AND
 BRANCH PIPING INSTALLED UNDER PERMIT- 01030466 AND THE
 GAS GENERATOR INSTALLED UNDER PERMIT- 06040973. PERMIT-
 0130466 INDICATES A TOTAL LOAD OF 675,000 BTUH, AND
 PERMIT- 06040973 INDICATES A LOAD OF 550,000 BTUH FOR
 THE GENERATOR- SECTION 107.2.1 WPB AND SECTIONS G2412.3
 & G2412.4 FBC RES.
  
 A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS
 OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION
 G2421.2(7) FBC RES.
  
 D) THE 1 IN. SCH 40 METALLIC PIPE IS UNDERSIZED FOR THE
 638,000 BTUH IS UNDERSIZED ACCORDING TO SIZING TABLE
 402.4(2) FBC FG THAT IS LISTED ON THE RISER.
  
 2) THE SURVEY SHOWS A 5 FT. CLEARANCE FROM THE
 GENERATOR EXHAUST TO OPENINGS INTO THE HOUSE HOWEVER A
 MINIMUM 10 FT. CLEARANCE IS REQUIRED TO MECHANICAL AND
 GRAVITY AIR INTAKES INTO THE BUILDING- SECTION-R303.5.1
 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER