Plan Review Notes
Plan Review Notes For Permit 20100947
Permit Number 20100947
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-22 15:58:2310/22/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 2. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW WILL
 BE REQUIRED AT THE WATER METER BY A LICENSED CONTRACTOR
 WITH A SEPARATE PERMIT. THE RPZ WILL NEED TO BE
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT AND THE CROSS CONNECTION CONTROL MANUAL.
 THIS IS DUE TO THE AUTOFILL WHICH WILL REQUIRE A
 BACKFLOW (PVB) FOR IT. THIS IS AN ISOLATION BACKFLOW
 AND IT WILL BE REQUIRED TO BE CERTIFIED BY A LICENSED
 BACKFLOW CONTRACTOR. A REPORT MUST BE FILLED OUT AND BE
 WITH THE PERMIT AT FINAL AS THE INSPECTOR MUST TAKE FOR
 CITY RECORDS.
  
 3. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP
 FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  