Date |
Text |
2020-10-22 15:58:23 | 10/22/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SIGNED AND SEALED DRAWINGS NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| ASKING FOR THE FORM. |
| |
| 2. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW WILL |
| BE REQUIRED AT THE WATER METER BY A LICENSED CONTRACTOR |
| WITH A SEPARATE PERMIT. THE RPZ WILL NEED TO BE |
| CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| DEPARTMENT AND THE CROSS CONNECTION CONTROL MANUAL. |
| THIS IS DUE TO THE AUTOFILL WHICH WILL REQUIRE A |
| BACKFLOW (PVB) FOR IT. THIS IS AN ISOLATION BACKFLOW |
| AND IT WILL BE REQUIRED TO BE CERTIFIED BY A LICENSED |
| BACKFLOW CONTRACTOR. A REPORT MUST BE FILLED OUT AND BE |
| WITH THE PERMIT AT FINAL AS THE INSPECTOR MUST TAKE FOR |
| CITY RECORDS. |
| |
| 3. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR |
| THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP |
| FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS |
| INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| EXCEPT THE PUMP. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |