Plan Review Notes For Permit 20100939 |
Permit Number |
20100939 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-04-06 10:32:47 | GENERATOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) THE PROVIDED ENGINEERING FROM "ENGINEERING EXPRESS" | | IS FOR THE GENERATOR CABINET FRAMING AND DOES NOT | | INCLUDE GENERATOR TIE DOWNS. PLEASE PROVIDE SIGNED AND | | SEALED GENERATOR TIE DOWNS FROM AN ENGINEER OR | | ARCHITECT. UNABLE TO FIND GENERATOR TIEDOWNS ON THE NEW | | DRAWINGS. GENERATOR IS SUBJECT TO WIND LOADS PLEASE | | PROVIDE TIE DOWNS TO COMPLY WITH WIND LOADS FBC 1609 | | AND SHOWING THE WIND DESIGN CRITERIA FBC 1603.1.4 | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN SUBMIT THE | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | BUILDING DIVISION AT CITY HALL. |
|