Plan Review Notes
Plan Review Notes For Permit 20100939
Permit Number 20100939
Review Stop B
Sequence Number 2
Notes
Date Text
2021-03-09 08:10:46GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) UNABLE TO FIND GENERATOR TIEDOWNS ON THE NEW
 DRAWINGS. GENERATOR IS SUBJECT TO WIND LOADS PLEASE
 PROVIDE TIE DOWNS TO COMPLY WITH WIND LOADS FBC 1609
 AND SHOWING THE WIND DESIGN CRITERIA FBC 1603.1.4
  
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN SUBMIT THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 BUILDING DIVISION AT CITY HALL.