Plan Review Notes
Plan Review Notes For Permit 20100939
Permit Number 20100939
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-03 16:02:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE SPECIFIC INDICATIONS OF THE EXHAUST
 LOCATION.
  
 PLEASE PROVIDE DETAILS OF THE EXHAUST LOCATION WITH
 SPECIFIC INTEREST TO THE FUMES ENTERING LIVING SPACES.
  
 PER NFPA 110 & 37
  
 NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
 NFPA 37
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE DETAILS
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  