Plan Review Notes
Plan Review Notes For Permit 20100933
Permit Number 20100933
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-01 19:28:142/1/2021 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
 THAT HAVE NOT BEEN ADDRESSED BELOW.
  
 1. A UNDERGROUND UTILITY CONTRACTOR IS NOT ALLOWED TO
 INSTALL THIS DEVICE UNLESS HE HAS THOSE LICENSE
 REFERRED BELOW.
  
 A GENERAL CONTRACTOR OR AN UNDERGROUND UTILITY AND
 EXCAVATION CONTRACTOR CANNOT INSTALL A BACKFLOW DEVICE
 PER THE 2019 FLORIDA STATUTES TITLE XXXII CHAPTER
 489.105(N). PLEASE PROVIDE THE PERMITTING DEPARTMENT
 WITH A VALID STATE OF FLORIDA LICENSED CONTRACTOR ALONG
 WITH AN APPLICATION.
  
 FS 489.105 DEFINITIONS.-- AS USED IN THIS PART:
 (1) "BOARD" MEANS THE CONSTRUCTION INDUSTRY LICENSING
 BOARD.
 (2) "DEPARTMENT" MEANS THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 (3) "CONTRACTOR" MEANS THE PERSON WHO IS QUALIFIED FOR,
 AND IS ONLY RESPONSIBLE FOR, THE PROJECT.
  
 (N) "UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR"
 MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE
 CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR
 PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN
 EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT
 LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING
 AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS,
 GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER
 COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS,
 STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF
 UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF
 TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR
 THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT
 PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY
 COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES
 AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT
 ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING
 SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER
 COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER,
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY,
 EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE
 DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO
 SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT
 SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL
 ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY,
 COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH
 CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR
 WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM.
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE
 PROTECTION SYSTEM AS DEFINED IN S. 633.102 BEGINNING AT
 THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH
 A SYSTEM.
  
 2. PLEASE PROVIDE MANUFACTURER?S SPECIFICATIONS FOR THE
 BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF THE
 DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE WORK
 SECTION ON THE PERMIT APPLICATION.
 A. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE
 WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD, PIPE
 FITTINGS, JOINTS, VALVES, FAUCETS AND FIXTURE FITTINGS
 UTILIZED TO SUPPLY WATER FOR DRINKING OR COOKING
 PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL HAVE A
 WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR LESS
 PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF
 DRINKING WATER PIPE AND FITTINGS.
  
 B. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  