2020-11-02 07:56:02 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100876 |
| 11/2/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS FROM THE 1ST REVIEW PRINTED BELOW ARE MARKED |
| AS PASSED OR FAILED. NOTES IN CAPS HAVE BEEN ADDED TO |
| FAILED COMMENTS. |
| |
| 1) PASSED. THE RISER INDICATES AN EXISTING METER |
| HOWEVER I WAS NOT ABLE TO LOCATE PERMITS AND PLAN |
| RECORDS OF EXISTING GAS PIPING AND EXISTING GAS-FIRED |
| APPLIANCES. A THOROUGH REVIEW CANNOT BE COMPLETED |
| WITHOUT A COMPLETE RISER DRAWING THAT INCLUDES THE |
| EXISTING GAS PIPING AND EXISTING APPLIANCES- SECTIONS |
| G2412.3 & G2412.4 FBC RES. PLEASE INDICATE THE DELIVERY |
| GAS PRESSURE AT THE METER. |
| |
| A) PASSED. SHOW THE CORRECT TOTAL LOAD AND THE |
| INDIVIDUAL LOADS OF THE SYSTEM- SECTIONS G2412.3, |
| G2412.4, & G2413.2 FBC RES. |
| |
| B) PASSED. PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF |
| THE PIPING FROM THE METER TO THE MOST REMOTE OUTLET, |
| AND THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 |
| AND G2413.4.2 FBC RES. |
| |
| C) FAILED. INDICATE THE INPUT GAS PRESSURE FOR THE |
| GENERATOR PER MANUFACTURER'S SPECIFICATIONS AT THE |
| OUTLET SIDE OF THE REGULATORS. PLEASE SUBMIT MARKED UP |
| OR HIGHLIGHTED SPECS FOR THE REGULATORS SHOWING THE |
| SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| PRESSURES, SPRING DATA, AND ORIFICE SIZE- SECTION |
| G2421. SHOW THE LOCATIONS OF THE NEW REGULATORS AT THE |
| NEW METER AND AT THE GENERATOR. SHOW THE INLET AND |
| OUTLET PRESSURES, AND LOCATIONS OF SHUTOFF VALVES. |
| |
| D) FAILED. SHOW THE REQUIRED PIPE UNIONS FOR RIGID |
| PIPING WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- |
| SECTION G2421.2(7). COMMENT NOT ADDRESSED. |
| |
| E) FAILED. PROVIDE THE PIPE SIZING TABLE- SEE TABLES |
| G2413.4(1)- G2413.4(8). COMMENT NOT ADDRESSED. |
| |
| 2) PASSED. THE SIGNATURE OF THE LICENSED CONTRACTOR OR |
| QUALIFIER SHALL BE ON THE RISER DRAWING- SECTION |
| 107.2.1 & FL. STATUTES 471.003(2) (H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |