2020-10-21 17:28:221ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100876
 10/21/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RISER INDICATES AN EXISTING METER HOWEVER I WAS
 NOT ABLE TO LOCATE PERMITS AND PLAN RECORDS OF EXISTING
 GAS PIPING AND EXISTING GAS-FIRED APPLIANCES. A
 THOROUGH REVIEW CANNOT BE COMPLETED WITHOUT A COMPLETE
 RISER DRAWING THAT INCLUDES THE EXISTING GAS PIPING AND
 EXISTING APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC
 RES. PLEASE INDICATE THE DELIVERY GAS PRESSURE AT THE
 METER.
  
 A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS
 OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR
 PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF
 THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED
 SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE
 MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 AND ORIFICE SIZE- SECTION G2421.
  
 D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION
 G2421.2(7).
  
 E) PROVIDE THE PIPE SIZING TABLE- SEE TABLES
 G2413.4(1)- G2413.4(8).
  
 2) THE SIGNATURE OF THE LICENSED CONTRACTOR OR
 QUALIFIER SHALL BE ON THE RISER DRAWING- SECTION
 107.2.1 & FL. STATUTES 471.003(2) (H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  