2020-10-21 17:28:22 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100876 |
| 10/21/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE RISER INDICATES AN EXISTING METER HOWEVER I WAS |
| NOT ABLE TO LOCATE PERMITS AND PLAN RECORDS OF EXISTING |
| GAS PIPING AND EXISTING GAS-FIRED APPLIANCES. A |
| THOROUGH REVIEW CANNOT BE COMPLETED WITHOUT A COMPLETE |
| RISER DRAWING THAT INCLUDES THE EXISTING GAS PIPING AND |
| EXISTING APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC |
| RES. PLEASE INDICATE THE DELIVERY GAS PRESSURE AT THE |
| METER. |
| |
| A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. |
| |
| B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| G2413.4.2 FBC RES. |
| |
| C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR |
| PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF |
| THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED |
| SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE |
| MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA, |
| AND ORIFICE SIZE- SECTION G2421. |
| |
| D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION |
| G2421.2(7). |
| |
| E) PROVIDE THE PIPE SIZING TABLE- SEE TABLES |
| G2413.4(1)- G2413.4(8). |
| |
| 2) THE SIGNATURE OF THE LICENSED CONTRACTOR OR |
| QUALIFIER SHALL BE ON THE RISER DRAWING- SECTION |
| 107.2.1 & FL. STATUTES 471.003(2) (H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |