2020-12-04 16:18:42 | PLAN REVIEW / BUILDING / FLOORING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 3RD REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. VALUE - CORRECTED | | | | | | NOTE: ASTM TEST REPORTS ARE REQUIRED - MANUFACTURER | | SPEC SHEETS ARE NOT ACCEPTABLE DUE TO DISCREPANCIES | | BETWEEN SPEC SHEETS/BROCHURES AND TEST REPORTS FOR SOME | | MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER | | SELECTED; THIS IS A GENERAL COMMENT) | | | | 2. PROVIDE THE FOLLOWING ASTM TEST REPORTS FOR THE | | PROPOSED UNDERLAYMENT. | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | | FBC 603.1 FLAME SPREAD ASTM E 84 OR UL 723 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|