Plan Review Notes
Plan Review Notes For Permit 20100857
Permit Number 20100857
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-27 14:16:41JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT THE
 FOLLOWING: COLUMN HEADING ?WALL PRESSURE?; PROVIDE THE
 ACTUAL [PSF] FROM THE SUBMITTED DESIGN PRESSURE
 CALCULATIONS. ?SHUTTER MOUNTING CONNECTION TYPE PER
 PRODUCT APPROVAL?; CONNECTION A HV WALL HEADER
 INSTALLATION REQUIRES POURED CONCRETE SUBSTRATE.
 ?SHUTTER GLASS SEPARATION?; PROVIDE INFORMATION FROM
 SHEET 11 FL1850. SHUTTERS NOT INSTALLED ABOVE 30?-0?
 ELEVATION OF BUILDING. COLUMN HEADING ?ANCHOR SPACING?
 VERIFY ALL ANCHOR SPACINGS FROM SHEETS 12-15 OF FL1850
 USING THE CORRECT DESIGN PRESSURES AND CONNECTION
 TYPES.
  