2020-10-26 08:45:18 | 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT- 20100843 |
| 10/23/2020 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE SUBMITTED APPLICATION IS FOR GAS PIPING |
| INSTALLATIONS. PLEASE REMOVE THE PLUMBING SHEETS THAT |
| ARE NOT ASSOCIATED WITH THE GAS WORK- SECTION 107.2.1 |
| WPB. |
| |
| 2) COPIES OF PREVIOUSLY APPROVED PLAN SHEETS UNDER A |
| SEPARATE PERMIT HAVE BEEN SUBMITTED WHICH ARE NOT |
| ACCEPTABLE. PROVIDE ORIGINAL, UP TO DATE, |
| ELECTRONICALLY SIGNED AND SEALED PLANS FOR GAS PERMIT |
| REVIEW- SECTION 107.2.1 WPB, FL. STATUTE 471.025, AND |
| SECTION 61G15-23.005. FAC. |
| |
| 3) PROVIDE A VALUE ON THE PERMIT APPLICATION THAT IS |
| CONSISTENT WITH THE SCOPE OF WORK SHOWN ON THE PLANS- |
| SECTION 109.3 WPB. IT APPEARS THAT THE PIPING |
| INSTALLATION COMPRISES MORE THAN JUST THE POOL PAVILION |
| BBG GRILLS. PLEASE PROVIDE AN ITEMIZED SCOPE OF WORK |
| AND PLANS THAT REFLECT THAT WORK. PLEASE SUBMIT COPIES |
| OF SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES THAT |
| VERIFY THE TOTAL COSTS OF LABOR, MATERIALS, AND |
| EQUIPMENT. |
| |
| 4) SHEET P-2.1 GAS RISER: |
| A) PROVIDE REVISED CIVIL PLANS SHOWING THE POINT OF |
| CONNECTION TO THE EXISTING MAIN GAS LINE AND THE |
| LOCATION OF THE NEW METER- SECTION 107.2.1 WPB. |
| B) SHOW THE DELIVERY PRESSURE AT THE METER- SECTION |
| 401.1 FBC FG. |
| C) SHOW THE TYPE AND SIZE OF RISER PIPES CONNECTING THE |
| UG PE TO THE REGULATOR AND THE METER- SECTIONS 401.8 & |
| 402.2 FBC FG. |
| D) SUBMIT MANUFACTURER'S SPECS FOR THE REGULATOR MARKED |
| OR HIGHLIGHTED UP TO SHOW THE SELECTED MODEL, INLET AND |
| OUTLET PIPE SIZES AND PRESSURES, AND ORIFICE SIZE- |
| SECTION 410.1 & 410.2 FBC FG. |
| E) SHOW THE LOCATIONS OF THE REQUIRED PIPE UNIONS AT |
| EACH SIDE OF THE REGULATOR- SECTION 410.2 (7). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |