Plan Review Notes
Plan Review Notes For Permit 20100843
Permit Number 20100843
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-26 08:45:181ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20100843
 10/23/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED APPLICATION IS FOR GAS PIPING
 INSTALLATIONS. PLEASE REMOVE THE PLUMBING SHEETS THAT
 ARE NOT ASSOCIATED WITH THE GAS WORK- SECTION 107.2.1
 WPB.
  
 2) COPIES OF PREVIOUSLY APPROVED PLAN SHEETS UNDER A
 SEPARATE PERMIT HAVE BEEN SUBMITTED WHICH ARE NOT
 ACCEPTABLE. PROVIDE ORIGINAL, UP TO DATE,
 ELECTRONICALLY SIGNED AND SEALED PLANS FOR GAS PERMIT
 REVIEW- SECTION 107.2.1 WPB, FL. STATUTE 471.025, AND
 SECTION 61G15-23.005. FAC.
  
 3) PROVIDE A VALUE ON THE PERMIT APPLICATION THAT IS
 CONSISTENT WITH THE SCOPE OF WORK SHOWN ON THE PLANS-
 SECTION 109.3 WPB. IT APPEARS THAT THE PIPING
 INSTALLATION COMPRISES MORE THAN JUST THE POOL PAVILION
 BBG GRILLS. PLEASE PROVIDE AN ITEMIZED SCOPE OF WORK
 AND PLANS THAT REFLECT THAT WORK. PLEASE SUBMIT COPIES
 OF SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES THAT
 VERIFY THE TOTAL COSTS OF LABOR, MATERIALS, AND
 EQUIPMENT.
  
 4) SHEET P-2.1 GAS RISER:
 A) PROVIDE REVISED CIVIL PLANS SHOWING THE POINT OF
 CONNECTION TO THE EXISTING MAIN GAS LINE AND THE
 LOCATION OF THE NEW METER- SECTION 107.2.1 WPB.
 B) SHOW THE DELIVERY PRESSURE AT THE METER- SECTION
 401.1 FBC FG.
 C) SHOW THE TYPE AND SIZE OF RISER PIPES CONNECTING THE
 UG PE TO THE REGULATOR AND THE METER- SECTIONS 401.8 &
 402.2 FBC FG.
 D) SUBMIT MANUFACTURER'S SPECS FOR THE REGULATOR MARKED
 OR HIGHLIGHTED UP TO SHOW THE SELECTED MODEL, INLET AND
 OUTLET PIPE SIZES AND PRESSURES, AND ORIFICE SIZE-
 SECTION 410.1 & 410.2 FBC FG.
 E) SHOW THE LOCATIONS OF THE REQUIRED PIPE UNIONS AT
 EACH SIDE OF THE REGULATOR- SECTION 410.2 (7).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER