2020-10-28 13:07:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100816 |
| 10/28/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: PLEASE INCLUDE THE 55,000 BTUH |
| BBQ GRILL IN THE EXISTING APPLIANCE LIST, AND CORRECT |
| THE MAX BTUH LOAD TOTAL TO INDICATE 991,000 BTUH. THE |
| GRILL WAS INCLUDED WITH THE APPROVED PLANS UNDER |
| PERMIT- 15110671 - SECTIONS G2412.3, G2412.4 & G2413.2 |
| FBC RES. |
| |
| A) USING PIPE SIZING TABLE 402.4(3) FBC FG THAT YOU |
| SHOW ON THE RISER, THE 1 IN. MAIN RISER PIPE IS |
| UNDERSIZED FOR A 911,000 BTUH LOAD AT A TOTAL DEVELOPED |
| LENGTH OF 110 FT. THE MINIMUM SIZE PER THE TABLE IS |
| 1-1/4 IN. |
| |
| 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE RISER |
| DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION |
| 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) & |
| 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |