Plan Review Notes For Permit 20100816 |
Permit Number |
20100816 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-02 08:44:39 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | 1) PLEASE SPECIFY SIZE OF BREAKER AT GENERATOR. | | 2) ARE ALL THE CONDUCTORS FROM GENERATOR TO TRANSFER | | SWITCH WITHIN THE SAME 1 1/4" CONDUIT? PLEASE CLARIFY | | AND SHOW ON DRAWINGS IF SEPARATED. | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|