Date |
Text |
2020-11-23 09:10:03 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100815 |
| 11/23/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017FBC B- |
| FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS #1A & 2 FROM THE 1ST REVIEW PRINTED BELOW |
| STILL EXIST. |
| |
| 1A) THE 1-1/2 IN. PE SUPPLYING THE POOL HEATER AND |
| GENERATOR IS UNDERSIZED BASED ON THE PIPE SIZING TABLE |
| YOU ARE SHOWING- TABLE 402.4(21) FBC FG. ACCORDING TO |
| THE TABLE A 1-1/2 IN. PE WILL SUPPLY A MAXIMUM 485,000 |
| BTU'S AT 125 FT. LENGTH. TABLE 402.4(21) HAS BEEN |
| REMOVED FROM THE DRAWING HOWEVER THE PIPE IS STILL |
| UNDERSIZED BASED ON ALL LOW PRESSURE PE PIPE SIZNG |
| TABLES IN THE FBC- 17 FUEL GAS. |
| |
| 2) THE SURVEY DRAWING IS INCORRECTLY INDICATING A 5 FT. |
| CLEARANCE FROM THE GENERATOR TO WINDOW AND DOOR |
| OPENINGS INTO THE BUILDING, HOWEVER A 10 FT. CLEARANCE |
| IS REQUIRED- SECTION R303.5.1 FBC RES. PLEASE CORRECT |
| THE DRAWING TO INDICATE THE REQUIRED 10 FT. CLEARANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |