2020-10-28 11:09:48PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. INCORRECT ADDRESS ON THE FOLLOWING PLAN PAGES:
 SITE PLAN
 BLDG. PERMIT APPLICATION
 ENERGY SUBMITTAL
  
 SEE ADDRESS REVIEW COMMENTS.
  
 2. PROVIDE FINISHED FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 3. DOOR NOA 18-0503.06 SUBMITTED FOR REVIEW IS NOT THE
 DOOR NOA ON THE DOOR SCHEDULE.
 SGD NOA 17-1212.05 IS NOT ON THE DOOR SCHEDULE.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  