Plan Review Notes
Plan Review Notes For Permit 20100733
Permit Number 20100733
Review Stop G
Sequence Number 2
Notes
Date Text
2020-12-04 09:55:202ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100733
 12/4/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BASED ON PIPE SIZING TABLE G2413.4(1) [402.4(2)] FBC
 RES. FUEL GAS THE 1/2 IN. SCHEDULE 40 GALVANIZED GAS
 PIPE IS UNDERSIZED TO SUPPLY THE 199,000 BTUH TANKLESS
 WATER HEATER. PLEASE PROVIDE A 3/4 IN. PIPE.
  
 2) BASED ON PAGE 5 ON THE RHEEM WATER HEATER
 INSTALLATION MANUAL THE GAS INPUT PRESSURE RANGE IS
 4.0- 10.5 IN. W.C. PLEASE PROVIDE A REGULATOR AT THE
 NEW WATER HEATER IN COMPLIANCE WITH SECTION G2421 FBC
 RES. SHOW THE MAKE AND MODEL OF THE REGULATOR ON THE
 PLAN AND SUBMIT SPECS MARKED UP OR HIGHLIGHTED TO THE
 SELECTED MODEL, INLET AND OUTLET PIPE SIZES AND
 PRESSURES, AND ORIFICE SIZE. SHOW THE REQUIRED PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR-
 SECTION 2421.2(7) FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  