Plan Review Notes
Plan Review Notes For Permit 20100709
Permit Number 20100709
Review Stop P
Sequence Number 2
Notes
Date Text
2022-10-04 16:46:202ND REVIEW FBC-2020 PLUMBING
 PERMIT-20100709
 10/4/24
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AE410 DETAILS A1 & B1: SHOW THE DEPTH AND
 WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACES AT THE
 ACCESSIBLE WATER CLOSETS, LAVATORIES, AND URINAL- SECS.
 604.3, 606.2 & 605.3 FBC ACC.
  
 2) AE410- A1: THE COMPARTMENT DOOR SHALL NOT SWING INTO
 THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY- SEC.
 603.2.3 FBC ACC.
  
 3) AE410- D2: THE TILE BACKER AT THE MOP SINK SHALL
 EXTEND 4FT. ABOVE THE SINK- SEC. 1210.2.2 FBC B.
  
 4) P-111 & P-201: A GREASE INTERCEPTOR IS REQUIRED TO
 RECEIVE THE GREASE LADEN DRAINAGE FROM THE
 3-COMPARTMENT SINK, THE MOP SINK, DISHWASHER, AND ANY
 OTHER SINKS, FLOOR DRAINS ETC. DISCHARGING GREASE LADEN
 WASTE- SEC. 1003.3.1 FBC P. REVISE THE PLANS TO SHOW
 THE LOCATION OF THE INTERCEPTOR AND PLUMBING PIPING
 DETAILS- SEC. 107.2.1 WPB.
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE INTERCEPTOR AND DUE TO A RECENT
 CHANGE IN PROCESS, THE INTERCEPTOR PERMIT IS REQUIRED
 TO BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY
 PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 5) P-200: AN ACCESSIBLE SHOWER (SH-1) IS SHOWN IN THE
 FIXTURE SCHEDULE HOWEVER THE LOCATION OF THE FIXTURE
 AND PIPING DETAILS ARE NOT SHOWN IN THE PLANS- SEC.
 1`07.2.1 WPB.
  
 6) P-111 & P-201: SHOW HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE PUBLIC LAVATORIES- SEC. 419.5 FBC P.
  
 7) P-111 & P-201: THE HW RECIRCULATION LOOP IS NOT
 DESIGNED IN COMPLIANCE WITH SEC. C404.5.1 FBC EC. THE
 1/2-INCH HW PIPES TO THE LAVATORIES ARE EXCEEDING THE
 MAXIMUM ALLOWABLE 2 FT. LENGTHS FROM THE HOT WATER
 SOURCE (RECIRCULATION LINE)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  