2022-10-04 06:55:362ND REVIEW FMC
 PERMIT: 20100709
  
 CODES IN EFFECT: 2020
  
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
  
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE SCOPE OF THIS PROJECT HAS CHANGED, THERE IS NO
 LONGER AN EXTERIOR FREEZER. THE SCOPE OF WORK FOR THE
 MECHANICAL NOW APPEARS TO BE AN ADDITION AND NEW
 MECHANICAL DESIGN IN EXISTING STRUCTURE.
  
 1) PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS STATING
 THAT ALL HOODS AND REFRIGERATION WILL REQUIRE SEPARATE
 PERMIT APPLICATIONS AND SEPARATE PLAN REVIEWS AND
 NEITHER WILL BE REVIEWED UNDER THIS PERMIT APPLICATION.
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FMC 312.1
  
 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE. PLEASE USE THE OCCUPANCY CLASSIFICATIONS
 PRESENTED IN FMC TABLE 403.3.1.1 THAT MOST CLOSELY
 RESEMBLES THE USE OF EACH SPACE. FMC 403.3.1.1
  
 4) SHEET M-111; PROVIDE THE DUCT SIZES FOR EACH DUCT IN
 THE SYSTEMS. FBC 107.3.5
  
 5) SHEET M-111; PLEASE SHOW THE RETURN AIR PATH FROM
 THE RETAIL SALES AREA BACK TO X-OAU-2. FBC 107.3.5
  
 6) SHEET M-111: THERE ARE 2 NOTES INDICATING -SEE UPPER
 FLOOR PLAN FOR CONTINUATION- SHEET M-112 SHOWS ONLY ONE
 BUT DOES NOT SHOW THE AREA IT SERVES. PLEASE SHOW BOTH
 SUPPLY DUCTS ON THE UPPER FLOOR PLAN AND CONTINUE THEM
 TO THE AREAS THEY SERVE. ALSO SHOW THE RETURN AIR PATH
 FROM THE UPPER FLOOR BACK TO OAU-3. FBC 107.3.5
  
 7) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF MEETS THE
 GUARD PROTECTION REQUIREMENTS IN FMC 304.11
  
 8) PLEASE SHOW THE MECHANICAL EQUIPMENT ON THE ROOF
 WILL MEET THE ACCESS REQUIREMENTS IN FMC 306.5
  
 9) PLEASE SHOW THE CONDENSATE PIPE MATERIAL AND
 TERMINATION LOCATION. FMC 307.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  