2021-10-05 14:56:02 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-20100709 |
| 10/5/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 1-G1003: THE PLUMBING FIXTURE CALCULATIONS |
| SHALL BE BASED ON THE FBC- 2020 7TH EDITION PLUMBING |
| CODE. PLEASE CORRECT THE OUTDATED CODE REFERENCE AND |
| REFER TO TABLE 403.1- DRINKING FOUNTAINS AND SERVICE |
| SINKS ARE REQUIRED PLUMBING FIXTURES. PLEASE SHOW THE |
| LOCATIONS OF THE FIXTURES ON THE DRAWINGS. |
| |
| 2) SHEETS 1-PD110 & 1-P-110: THE PLANS DO NOT SHOW ANY |
| CHANGES TO THE PLUMBING SYSTEMS EXCEPT FOR THE |
| CONDENSATE PIPING HOWEVER THE APPLICATION INDICATES |
| IMPROVEMENTS TO THE OFFICE/BAKERY AREAS. PLEASE CLARIFY |
| IF ANY ALTERATIONS TO THE PLUMBING SYSTEMS ARE PROPOSED |
| BASED ON THOSE ALTERATIONS- SECTION 107.2.1 WPB. |
| |
| 3) 1-PD110: SHOW THE TYPES AND SIZES OF THE CONDENSATE |
| PIPING- SECTION 314.2.2. FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |