Plan Review Notes
Plan Review Notes For Permit 20100709
Permit Number 20100709
Review Stop M
Sequence Number 1
Notes
Date Text
2021-09-24 15:06:031) PLEASE PROVIDE MECHANICAL DRAWINGS FOR THE
 MECHANICAL WORK FOR THE NEW FREEZER.
 2) PLEASE PROVIDE INFORMATION SHOWING THAT THE FACTORY
 BUILT FREEZER IS LISTED AND LABELED. FBC M 1101.2
 3) PLEASE PROVIDE THE SYSTEM REQUIREMENTS PER FBC M
 1102
 4) PROVIDE EQUIPMENT TIE DOWN INFORMATION FOR THE
 CONDENSING UNIT.
 5) PLEASE SHOW THE CONDENSATE PIPING AND TERMINATION
 LOCATION. FBC M 307
 6) PLEASE SHOW PROTECTION FROM VEHICULAR TRAFFIC FOR
 THE EXTERIOR OF THE FREEZER. FBC M 1101.3
 7) PLEASE PROVIDE INFORMATION SHOWING THAT THE NEW
 FREEZER MEETS THE ENERGY EFFICIENCY CODE. FBC EC
 C403.2.14
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  