Plan Review Notes For Permit 20100709 |
Permit Number |
20100709 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-24 15:06:03 | 1) PLEASE PROVIDE MECHANICAL DRAWINGS FOR THE | | MECHANICAL WORK FOR THE NEW FREEZER. | | 2) PLEASE PROVIDE INFORMATION SHOWING THAT THE FACTORY | | BUILT FREEZER IS LISTED AND LABELED. FBC M 1101.2 | | 3) PLEASE PROVIDE THE SYSTEM REQUIREMENTS PER FBC M | | 1102 | | 4) PROVIDE EQUIPMENT TIE DOWN INFORMATION FOR THE | | CONDENSING UNIT. | | 5) PLEASE SHOW THE CONDENSATE PIPING AND TERMINATION | | LOCATION. FBC M 307 | | 6) PLEASE SHOW PROTECTION FROM VEHICULAR TRAFFIC FOR | | THE EXTERIOR OF THE FREEZER. FBC M 1101.3 | | 7) PLEASE PROVIDE INFORMATION SHOWING THAT THE NEW | | FREEZER MEETS THE ENERGY EFFICIENCY CODE. FBC EC | | C403.2.14 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|