Plan Review Notes
Plan Review Notes For Permit 20100709
Permit Number 20100709
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-20 10:08:57EXTERIOR COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) CODE IN EFFECT HAS CHANGED ON 1/1/21 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE CODE IN EFFECT (2020 FBC USING
 ASCE 7-16)
 2) PLEASE SHOW THE TERMITE PREVENTION REQUIRED FOR THE
 NEW STRUCTURE - FBC 1816
 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE DESIGNER OF RECORD FBC WPB 107.3.4
 4) DRAWING S004 SHOULD SHOW THE RISK CATEGORY USED FOR
 WIND DESIGN FBC 1603.1.4 - SHOW THE CORRECT WIND SPEED
 USED FOR THE WIND DESIGN BASED ON THE RISK CATEGORY PER
 FBC WPB SECTION 120.
 5) PLEASE PROVIDE THE COOLER WALL AND ROOF PANEL
 DETAILS - DESCRIPTION OF WALL PANELS, ATTACHMENTS TO
 FOUNDATION, ATTACHMENTS OF PANEL TO PANEL ETC. TO
 COMPLY WITH THE WIND LOADS SHOWN ON DRAWING S004.