Plan Review Notes
Plan Review Notes For Permit 20100704
Permit Number 20100704
Review Stop G
Sequence Number 2
Notes
Date Text
2020-12-04 12:35:442ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 201000704
 12/4/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P103 GAS RISER:
  
 A) THE TOTAL GAS LOAD OF 1,178,000 BTUH AT A TOTAL
 DEVELOPED LENGTH OF 180 FT. WILL REQUIRE INSTALLATION
 OF A MINIMUM 1 IN. PE FROM THE METER TO THE FIRST
 BRANCH LINE TEE- TABLE 402.4(22) 2 PSI PRESSURE. THE
 RISER IS SHOWING A 3/4 IN. PIPE WHICH IS UNDERSIZED.
 B) THE 3/4 IN. SCHED. 40 GALVANIZED PIPE AT LOW
 PRESSURE OF 0.5 IN. W.C. SHOWN IMMEDIATELY AFTER REG. C
 IS UNDERSIZED TO SUPPLY THE TOTAL BRANCH LOAD OF
 478,000 BTUH AT 60 FT. TDL. ACCORDING TO TABLE 402.4(2)
 A MINIMUM 1-1/4 IN. PIPE IS REQUIRED.
 C) PLEASE CORRECT THE 6 FT. PIPE LENGTH UNDER REG. A
 SHOWN IN THE TABLE. THE RISER SHOWS A 50 FT. PIPE RUN
 TO THE COOKTOP. THE 1/2 IN. SCHEDULE 40 GALVANIZED PIPE
 AT THIS LOCATION IS UNDERSIZED- A 3/4 IN. PIPE IS
 REQUIRED PER TABLE 402.4(2). PLEASE NOTE A MINIMUM
 1-1/2 IN. SCHED. 40 PIPE IS REQUIRED AT REG. FOR A
 TOTAL BRANCH LOAD OF 550,000 BTUH LOAD AT 50 FT.- TABLE
 402.4(2). THE PIPE SIZE AT REG A IS NOT SPECIFIED
 HOWEVER AN UNDERSIZED 1/2 IN. PIPE IS SHOWN FOR THE
 400,000 BTUH POOL HEATER- A MINIMUM 1-1/4 IN. PIPE IS
 REQUIRED.
  
 2) THE ARCHITECT OF RECORD WHO PREPARED SHEET P103
 SHALL PROVIDE HIS/HER DIGITAL SEAL AND SIGNATURE ON THE
 PLAN- FLORIDA STATUTE 481.221 AND SECTION 61G1- 16.005
 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  