Plan Review Notes
Plan Review Notes For Permit 20100675
Permit Number 20100675
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-22 16:59:221ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20100675
 10/22/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-3: THE 2 IN. WASHING MACHINE STANDPIPE DRAIN
 SHALL CONNECT TO A 3 IN. STACK OR HORIZONTAL BRANCH
 DRAIN- SECTION 406.2 FBC P.
  
 2) A-3 SHOWER DETAIL: SHOW AN APPROVED PAN LINER WILL
 BE INSTALLED IN ACCORDANCE WITH SECTIONS 417.5.2-
 417.5.2.6 FBC P, AND INDICATE IT WILL BE SLOPED TO THE
 DRAIN AT A PITCH OF 1/4 IN PER FT.
  
 3) A-2 & A-3: PLEASE PLACE A NOTE TO CLARIFY IF THE TUB
 DRAIN WILL BE RELOCATED FOR THE NEW SHOWER OR IF IT
 WILL REMAIN IN THE SAME LOCATION. A SANITARY RISER IS
 REQUIRED FOR RELOCATED DRAINS AND VENTS- SECTIONS 701.1
 AND 901.1 FBC P.
  
 4) A-2 & A-3: PLACE A NOTE TO INDICATE THE NEW SHOWER
 VALVE SHALL MEET COMPLIANCE WITH SECTION 424.3 FBC P
 AND SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1.
  
 5) A-2 & A-3: SHOW THE LOCATIONS OF THE NEW WASHING
 MACHINE VALVES AND PLACE A NOTE SHOWING IT WILL BE
 INSTALLED IN AN ACCESSIBLE LOCATION- SECTION 606.3 FBC
 P.
  
 6) A-2 & A-3: PROVIDE A WATER RISER DRAWING FOR THE
 WASHING MACHINE SHOWING SUPPLY PIPING, REQUIRED WATER
 HAMMER ARRESTORS, AND POINTS OF CONNECTION TO THE
 EXISTING WATER LINES- SECTION 604.9 FBC P. AS AN
 ALTERNATE TO A RISER DRAWING, NOTES ON THE PLAN ARE
 ACCEPTABLE.
  
 7) A-2 & A-3: PROVIDE A SLAB REPAIR DETAIL- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  