Plan Review Notes For Permit 20100675 |
Permit Number |
20100675 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-29 16:09:44 | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, | | SEE COMMENTS BELOW | | | | ALL RECEPTACLES IN KITCHEN AREA MUST BE GFCI PROTECTED | | (NOT JUST THE COUNTER RECEPTACLES). NEC 210.8 (B)(2) |
|