Plan Review Notes For Permit 20100646 |
Permit Number |
20100646 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-11-06 14:56:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE TWO NEW SHEETS SUBMITTED WITH THE ORIGINAL | | SHEETS DELETED. | | | | THE ORIGNAL SHEETS NEED TO BE INCLUDED AS SOME OF THE | | INFOAMTION WAS ACCEPTABLE AND NEEDS TO REPRESENTED | | | | | | | | 2) THE NEW SHEETS INDICATE SOME NUMBERS BUT I DON'T | | KNOW WHAT THOSE NUMBERS EQUATE TO IN INCHES. | | | | PLEASE CLARIFY. | | | | | | 2A) WHAT WILL THE HEIGHT BE TO THE TOP OF THE GLASS | | ABOVE THE FLAME? | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|