Plan Review Notes For Permit 20100635 |
Permit Number |
20100635 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-15 11:09:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO DETAIL ON THE SITE PLAN INDICATING WHERE | | THE SCREEN IS LOCATED, PROJECTOR LOCATION, PROTECTED | | POWER SUPPLIES, TRAFFIC PATTERN, PEDESTRIAN EXIT | | ACCESS(IN THE EVENT THE NEED TO LEAVE THEIR VEHICLES IN | | EMERGENCY), | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 2) A BOX DINNER IS INDICATED, WILL THIS BE PREPARED ON | | SITE? HOW? ARE FOOD TRUCKS SCHEDULED? | | | | PLEASE PROVIDE DETAILS | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|