2020-10-31 11:48:26PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
  
 BUILDING REVIEW DENIED:
  
 PLEASE CLARIFY AND PROVIDE INFORMATION ON A SCHEDULE AS
 NOTED BELOW:
  
 FBC B 107.2.1, PRODUCT APPROVAL # 16893-R5, PAGE #18
 HAS BEEN MARKED FOR A SPAN OF 60" FOR A 9" O.C. ANCHOR
 SPACING BUT THE PROVIDED WINDLOAD CHART INDICATES THE
 SPAN SHOULD BE AT A SPAN OF 96" FOR ANCHOR SPACING OF
 6" O.C..
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.
  