2020-10-27 14:15:40 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100549 |
| 10/27/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) LP GAS TANK AND INSTALLATION SPECS HAVE BEEN |
| INCORRECTLY SUBMITTED. PLEASE PROVIDE A NATURAL GAS |
| SUBMITTAL PACKAGE THAT INCLUDES THE GENERATOR FLEX |
| CONNECTOR, REGULATOR, AND PIPE SIZING TABLES- SECTION |
| 107.2.1 WPB. |
| |
| 2) GAS RISER DRAWING: PLEASE INCLUDE THE 22,000 BTUH |
| DRYER IN THE EXISTING APPLIANCE LIST, AND CORRECT THE |
| BTUH LOAD TOTAL TO INDICATE 869,000 BTUH. THE DRYER WAS |
| INCLUDED WITH THE APPROVED PLANS UNDER PERMIT- |
| 99100191- SECTIONS G2412.3, G2412.4 & G2413.2 FBC RES. |
| |
| A) INDICATE THE RISER PIPE SIZES AT THE METER- SECTION |
| G2413.1 FBC RES. PLEASE NOTE THE PIPE SIZING TABLE |
| 402.4(3) FBC FG YOU SHOW ON THE RISER INDICATES A |
| MINIMUM 1-1/4 IN. MAIN SUPPLY PIPE IS REQUIRED FOR A |
| 869,000 BTUH SYSTEM AT A TOTAL DEVELOPED LENGTH OF 110 |
| FT. |
| |
| B) A REGULATOR AT THE GENERATOR IS REQUIRED TO DROP THE |
| PRESSURE TO 3.5- 7 IN. W.C PER THE GENERATOR SPECS- |
| SECTION 2421.1 FBC RES. SHOW THE REGULATOR ON THE RISER |
| AND THE REQUIRED PIPE UNIONS PER SECTION 2421.2(7) FBC |
| RES. SUBMIT MANUFACTURER?S SPECIFICATIONS MARKED UP OR |
| HIGHLIGHTED TO SHOW THE SELECTED MODEL, INPUT AND |
| OUTPUT PIPE SIZE AND PRESSURE, AND ORIFICE SIZE. |
| |
| 2) CORRECT THE SURVEY DRAWING TO INDICATE A 10 FT. |
| CLEARANCE FOR THE GENERATOR TO MECHANICAL AND GRAVITY |
| AIR INTAKES (OPERABLE WINDOWS AND DOORS) INTO THE |
| RESIDENCE- SECTION R303.5.1 FBC RES. |
| |
| 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |